XHHW-2 dimensions

Nominal calculation, not one manufacturer's datasheet. The conductor is NEC Chapter 9 Table 8; the insulation and nylon walls are the nominal values the makers catalogue, because UL 83, UL 44 and UL 854 were not read. A wire of the same name can differ slightly: check its datasheet before you specify or order.

Each row is one XHHW-2 size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What XHHW-2 means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 24 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
14 AWG600 V0.763.320
12 AWG600 V0.763.840
10 AWG600 V0.764.460
8 AWG600 V1.145.990
6 AWG600 V1.146.8140
4 AWG600 V1.148.0210
3 AWG600 V1.148.7270
2 AWG600 V1.149.5330
1 AWG600 V1.4011.0420
1/0 AWG600 V1.4012.0530
2/0 AWG600 V1.4013.1660
3/0 AWG600 V1.4014.4820
4/0 AWG600 V1.4015.81,030
250 kcmil600 V1.6517.51,230
300 kcmil600 V1.6518.81,460
350 kcmil600 V1.6520.11,690
400 kcmil600 V1.6521.21,930
500 kcmil600 V1.6523.32,400
600 kcmil600 V2.0326.12,900
700 kcmil600 V2.0327.83,370
750 kcmil600 V2.0328.73,600
800 kcmil600 V2.0329.53,830
900 kcmil600 V2.0331.04,310
1000 kcmil600 V2.0332.44,780

Who makes or stocks this cable?