URD
URD is a NEC / UL (USA) cable designation: URD = Underground residential distribution (reading by usage); URD = Underground residential distribution cable, twisted aluminium conductors, direct burial. 600 V, 90 C XLPE. UL 854; ICEA / NEMA WC 70.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: UL 1072: Medium-Voltage Power Cables. How the values are sourced
Worked reading of URD 1/0 AWG, 15 kV 100 %:
URD: URD = Underground residential distribution (reading by usage); URD = Underground residential distribution cable, twisted aluminium conductors, direct burial. 600 V, 90 C XLPE. UL 854; ICEA / NEMA WC 701/0 AWG, 15 kV 100 %: one core, copper 1/0 AWG (53.5 mm²); rated voltage 15 kV 100 %
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
URD | Underground residential distribution (reading by usage) |
URD | Underground residential distribution cable, twisted aluminium conductors, direct burial. 600 V, 90 C XLPE. UL 854; ICEA / NEMA WC 70 |
What is URD cable?
URD: Underground residential distribution cable, twisted aluminium conductors, direct burial. Rating: 600 V, 90 C XLPE. Standard: UL 854; ICEA / NEMA WC 70.
Triplex: two phase conductors and one neutral twisted together, e.g. 4-4-4. Aluminium by default.
Documents and pages the readings were taken from
URD as the cable designer builds it, 1/0 AWG, 15 kV 100 %
Overall diameter 28.0 mm, about 1,350 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.48 | 10.2 |
| Insulation | XLPE | 4.4 | 19.0 |
| Insulation screen (semicon) | Semiconducting | 1.1 | 21.3 |
| Wire screen | Copper | 16 × 2.05 | 25.4 |
| Sheath | PE | 1.3 | 28.0 |
URD on a drum
The smallest drum that passes every check, for 28 mm and about 1,350 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite | 7 of 12 | 760–825 kg |
| 1,000 m | NEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite | 12 of 12 | 1,435–1,500 kg |
Barrel at least 25 × OD = 700 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: URD
URD belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Terms on this page: direct burial
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with URD
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.