URD

URD is a NEC / UL (USA) cable designation: URD = Underground residential distribution (reading by usage); URD = Underground residential distribution cable, twisted aluminium conductors, direct burial. 600 V, 90 C XLPE. UL 854; ICEA / NEMA WC 70.

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: UL 1072: Medium-Voltage Power Cables. How the values are sourced

Worked reading of URD 1/0 AWG, 15 kV 100 %:

  • URD: URD = Underground residential distribution (reading by usage); URD = Underground residential distribution cable, twisted aluminium conductors, direct burial. 600 V, 90 C XLPE. UL 854; ICEA / NEMA WC 70
  • 1/0 AWG, 15 kV 100 %: one core, copper 1/0 AWG (53.5 mm²); rated voltage 15 kV 100 %

NEC / UL (USA)

SymbolMeaning
URDUnderground residential distribution (reading by usage)
URDUnderground residential distribution cable, twisted aluminium conductors, direct burial. 600 V, 90 C XLPE. UL 854; ICEA / NEMA WC 70

What is URD cable?

URD: Underground residential distribution cable, twisted aluminium conductors, direct burial. Rating: 600 V, 90 C XLPE. Standard: UL 854; ICEA / NEMA WC 70.

Triplex: two phase conductors and one neutral twisted together, e.g. 4-4-4. Aluminium by default.

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

URD as the cable designer builds it, 1/0 AWG, 15 kV 100 %

Overall diameter 28.0 mm, about 1,350 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.4810.2
InsulationXLPE4.419.0
Insulation screen (semicon)Semiconducting1.121.3
Wire screenCopper16 × 2.0525.4
SheathPE1.328.0

URD on a drum

The smallest drum that passes every check, for 28 mm and about 1,350 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite7 of 12760–825 kg
1,000 mNEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite12 of 121,435–1,500 kg

Barrel at least 25 × OD = 700 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: URD

URD belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Terms on this page: direct burial

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with URD

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations

URD