NM-B
NM-B is a NEC / UL (USA) cable designation: NM = Non-metallic sheathed cable; -B = Conductors rated 90 C; NM-B = Non-metallic sheathed cable, type B (90 C conductors), for dry indoor wiring. 600 V, 90 C conductors (ampacity at the 60 C column). UL 719; NEC Article 334.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: UL 719: Nonmetallic-Sheathed Cables. How the values are sourced
Worked reading of NM-B 2/C 12 AWG, 600 V:
NM-B: NM = Non-metallic sheathed cable; -B = Conductors rated 90 C; NM-B = Non-metallic sheathed cable, type B (90 C conductors), for dry indoor wiring. 600 V, 90 C conductors (ampacity at the 60 C column). UL 719; NEC Article 3342/C 12 AWG, 600 V: 2 cores, each copper 12 AWG (3.3 mm²); rated voltage 600 V
Related cable types: nm
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
NM | Non-metallic sheathed cable |
-B | Conductors rated 90 C |
NM-B | Non-metallic sheathed cable, type B (90 C conductors), for dry indoor wiring. 600 V, 90 C conductors (ampacity at the 60 C column). UL 719; NEC Article 334 |
What is NM-B cable?
NM-B: Non-metallic sheathed cable, type B (90 C conductors), for dry indoor wiring. Rating: 600 V, 90 C conductors (ampacity at the 60 C column). Standard: UL 719; NEC Article 334.
Romex is Southwire's brand, used as the type name. "NM" alone also reads here (the older 60 C type has the same build).
Documents and pages the readings were taken from
NM-B as the cable designer builds it, 2/C 12 AWG, 600 V
Flat, 10.0 × 4.7 mm (width × thickness), about 130 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.38 | 2.8 |
| Nylon jacket (polyamide) | Nylon (PA) | 0.10 | 3.0 |
| Ground conductor: Separation tape | Paper | 0.10 | 2.3 |
| Separation tape | Paper | 0.10 | 3.2 |
| Sheath | PVC | 0.76 | 4.7 |
NM-B on a drum
The smallest drum that passes every check, for 10 mm and about 130 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 24x18x10, wood NEMA reels (North America), American Wire Group, Okonite | 11 of 13 | 76–79 kg |
| 1,000 m | NEMA 30x18x12, wood NEMA reels (North America), American Wire Group, Okonite | 17 of 19 | 148–150 kg |
Barrel at least 15 × OD = 150 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: NM-B
NM-B belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with NM-B
Who makes or stocks this cable?