THHN

THHN is a NEC / UL (USA) cable designation: T = Thermoplastic (PVC) insulation; HH = High heat resistant, 90 C (one H means 75 C); N = Nylon outer covering; THHN = Thermoplastic high heat-resistant nylon-coated building wire. 600 V, 90 C dry and damp locations. UL 83; NEC Article 310.

3 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: UL 83 (edition 16): Thermoplastic-Insulated Wires and Cables. How the values are sourced

Worked reading of THHN 12 AWG, 600 V:

  • THHN: T = Thermoplastic (PVC) insulation; HH = High heat resistant, 90 C (one H means 75 C); N = Nylon outer covering; THHN = Thermoplastic high heat-resistant nylon-coated building wire. 600 V, 90 C dry and damp locations. UL 83; NEC Article 310
  • 12 AWG, 600 V: one core, copper 12 AWG (3.3 mm²); rated voltage 600 V

Related cable types: THHN/THWN-2 · THHN-LS · ECOPLUS THHN

NEC / UL (USA)

SymbolMeaning
TThermoplastic (PVC) insulation
HHHigh heat resistant, 90 C (one H means 75 C)
NNylon outer covering
THHNThermoplastic high heat-resistant nylon-coated building wire. 600 V, 90 C dry and damp locations. UL 83; NEC Article 310

NEC Article 310 (US building wire, NFPA 70)

SymbolMeaning
TThermoplastic Insulation
HH90°C Insulation
NNylon Jacket

How to read a NEC Article 310 (US building wire, NFPA 70) cable code

NEC Article 402 (US fixture wires, NFPA 70)

SymbolMeaning
TThermoplastic Insulation
HH90°C Insulation
NNylon Jacket

How to read a NEC Article 402 (US fixture wires, NFPA 70) cable code

What is THHN cable?

THHN: Thermoplastic high heat-resistant nylon-coated building wire. Rating: 600 V, 90 C dry and damp locations. Standard: UL 83; NEC Article 310.

Usually dual-marked THHN/THWN-2 (and MTW when stranded): the reader treats each name as one listing of the same wire.

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

THHN dimensions and weight

Every THHN size

THHN: equivalents in other countries

Shown for 1x3.31 600 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)IEC 60502no letters for this buildCloseInsulation 0.38 → 1 mm; Overall diameter 3.23 → 4.47 mm

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

THHN as the cable designer builds it, 12 AWG, 600 V

Overall diameter 3.2 mm, about 40 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.383.0
Nylon jacket (polyamide)Nylon (PA)0.103.2

THHN on a drum

The smallest drum that passes every check, for 3.2 mm and about 40 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 14x10x5, wood NEMA reels (North America), Okonite13 of 2122 kg
1,000 mNEMA 18x10x6, wood NEMA reels (North America), Okonite21 of 3445 kg

Barrel at least 20 × OD = 65 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: THHN

THHN belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²