THHN dimensions

Nominal calculation, not one manufacturer's datasheet. The conductor is NEC Chapter 9 Table 8; the insulation and nylon walls are the nominal values the makers catalogue, because UL 83, UL 44 and UL 854 were not read. A wire of the same name can differ slightly: check its datasheet before you specify or order.

Each row is one THHN size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What THHN means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 24 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
14 AWG600 V0.382.820
12 AWG600 V0.383.240
10 AWG600 V0.514.160
8 AWG600 V0.765.490
6 AWG600 V0.766.3140
4 AWG600 V1.028.1230
3 AWG600 V1.028.7280
2 AWG600 V1.029.5350
1 AWG600 V1.2711.1450
1/0 AWG600 V1.2712.1550
2/0 AWG600 V1.2713.2690
3/0 AWG600 V1.2714.5850
4/0 AWG600 V1.2715.91,060
250 kcmil600 V1.5217.61,270
300 kcmil600 V1.5219.01,510
350 kcmil600 V1.5220.21,750
400 kcmil600 V1.5221.41,990
500 kcmil600 V1.5223.52,460
600 kcmil600 V1.7826.02,970
700 kcmil600 V1.7827.83,450
750 kcmil600 V1.7828.63,680
800 kcmil600 V1.7829.43,920
900 kcmil600 V1.7831.04,390
1000 kcmil600 V1.7832.44,870