THHN THWN-2 6 AWG 600 V

Nominal calculation, not one manufacturer's datasheet. The conductor is NEC Chapter 9 Table 8; the insulation and nylon walls are the nominal values the makers catalogue, because UL 83, UL 44 and UL 854 were not read. A wire of the same name can differ slightly: check its datasheet before you specify or order.

By NEC Table 8 and the catalogued walls, THHN THWN-2 6 AWG 600 V comes to an overall diameter of about 6.3 mm and a weight of about 140 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorCopper 6 AWG (13.3 mm²), Ø 4.5 mmcompressed Class B: ICEA S-94-649 Table C-4 as Elastimold prints it; below 2 AWG NEC Table 8 x 0.97 (its note)
InsulationPVC 0.76 mmTHHN / THWN-2 PVC insulation: Southwire and Cerrowire catalogue values (UL 83 is paywalled, not read)
Diameter over insulation6.1 mm
Overall diameter6.3 mm
Weight (approximate)140 kg/km

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationPVC0.766.1THHN / THWN-2 PVC insulation: Southwire and Cerrowire catalogue values (UL 83 is paywalled, not read)maker catalogue value, standard text not read
2Nylon jacket (polyamide)Nylon (PA)0.136.3THHN / THWN-2 nylon jacket: Southwire and Cerrowire catalogue values (UL 83 not read)maker catalogue value, standard text not read

THHN / THWN-2, XHHW-2 and USE-2 / RHW-2 are UL type names, not VDE ones: one conductor, its insulation and (THHN) a nylon jacket, no sheath. The conductor is compressed Class B stranding, as North American building wire is made. Sources: research/designer-americas in the site repository.

Materials in this cable: Copper, PVC

Weight, by part

Conductors120 kg/km
Metal screens and armour0 kg/km
Insulation, semicon, tapes, fillers and sheaths20 kg/km
Total140 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

Who makes or stocks this cable?

THHN

Other sections