UF-B

UF-B is a NEC / UL (USA) cable designation: UF = Underground feeder, direct burial; -B = Conductors rated 90 C; UF-B = Underground feeder cable, type B, sunlight-resistant gray jacket, direct burial. 600 V, 90 C conductors (ampacity at the 60 C column). UL 493; NEC Article 340.

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: UL 493: Thermoplastic-Insulated Underground Feeder and Branch-Circuit Cables. How the values are sourced

Worked reading of UF-B 2/C 12 AWG, 600 V:

  • UF-B: UF = Underground feeder, direct burial; -B = Conductors rated 90 C; UF-B = Underground feeder cable, type B, sunlight-resistant gray jacket, direct burial. 600 V, 90 C conductors (ampacity at the 60 C column). UL 493; NEC Article 340
  • 2/C 12 AWG, 600 V: 2 cores, each copper 12 AWG (3.3 mm²); rated voltage 600 V

NEC / UL (USA)

SymbolMeaning
UFUnderground feeder, direct burial
-BConductors rated 90 C
UF-BUnderground feeder cable, type B, sunlight-resistant gray jacket, direct burial. 600 V, 90 C conductors (ampacity at the 60 C column). UL 493; NEC Article 340

What is UF-B cable?

UF-B: Underground feeder cable, type B, sunlight-resistant gray jacket, direct burial. Rating: 600 V, 90 C conductors (ampacity at the 60 C column). Standard: UL 493; NEC Article 340.

The jacket is moulded around the parallel conductors and the bare ground (no paper filler).

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

UF-B as the cable designer builds it, 2/C 12 AWG, 600 V

Flat, 11.6 × 5.1 mm (width × thickness), about 150 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.382.8
Nylon jacket (polyamide)Nylon (PA)0.103.0
SheathPVC1.05.1

UF-B on a drum

The smallest drum that passes every check, for 11.6 mm and about 150 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 24x18x10, wood NEMA reels (North America), American Wire Group, Okonite12 of 1286–89 kg
1,000 mNEMA 32x24x14, wood NEMA reels (North America), American Wire Group, Okonite14 of 16175–180 kg

Barrel at least 15 × OD = 173 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: UF-B

UF-B belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Terms on this page: direct burial

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with UF-B

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations