THWN-2
THWN-2 is a NEC / UL (USA) cable designation: T = Thermoplastic (PVC) insulation; H = Heat resistant; W = Approved for wet locations; N = Nylon outer covering; -2 = 90 C in both wet and dry locations; THWN-2 = Thermoplastic heat- and water-resistant nylon-coated building wire, 90 C wet or dry. 600 V, 90 C wet and dry locations. UL 83; NEC Article 310.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: UL 83 (edition 16): Thermoplastic-Insulated Wires and Cables. How the values are sourced
Worked reading of THWN-2 12 AWG, 600 V:
THWN-2: T = Thermoplastic (PVC) insulation; H = Heat resistant; W = Approved for wet locations; N = Nylon outer covering; -2 = 90 C in both wet and dry locations; THWN-2 = Thermoplastic heat- and water-resistant nylon-coated building wire, 90 C wet or dry. 600 V, 90 C wet and dry locations. UL 83; NEC Article 31012 AWG, 600 V: one core, copper 12 AWG (3.3 mm²); rated voltage 600 V
Related cable types: THHN/THWN-2
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
T | Thermoplastic (PVC) insulation |
H | Heat resistant |
W | Approved for wet locations |
N | Nylon outer covering |
-2 | 90 C in both wet and dry locations |
THWN-2 | Thermoplastic heat- and water-resistant nylon-coated building wire, 90 C wet or dry. 600 V, 90 C wet and dry locations. UL 83; NEC Article 310 |
NEC Article 310 (US building wire, NFPA 70)
| Symbol | Meaning |
|---|---|
T | Thermoplastic Insulation |
H | 75°C Insulation |
W | Moisture Resistant |
N | Nylon Jacket |
-2 | With Insulation For Use In Wet Or Dry Locations At Max. Temp. 90°C |
How to read a NEC Article 310 (US building wire, NFPA 70) cable code
What is THWN-2 cable?
THWN-2: Thermoplastic heat- and water-resistant nylon-coated building wire, 90 C wet or dry. Rating: 600 V, 90 C wet and dry locations. Standard: UL 83; NEC Article 310.
Documents and pages the readings were taken from
THHN dimensions and weight
- THHN 14 AWG 600 V
- THHN 12 AWG 600 V
- THHN 10 AWG 600 V
- THHN 8 AWG 600 V
- THHN 6 AWG 600 V
- THHN 4 AWG 600 V
- THHN 3 AWG 600 V
- THHN 2 AWG 600 V
- THHN 1 AWG 600 V
- THHN 1/0 AWG 600 V
- THHN 2/0 AWG 600 V
- THHN 3/0 AWG 600 V
- THHN 4/0 AWG 600 V
- THHN 250 kcmil 600 V
- THHN 300 kcmil 600 V
- THHN 350 kcmil 600 V
- THHN 400 kcmil 600 V
- THHN 500 kcmil 600 V
- THHN 600 kcmil 600 V
- THHN 700 kcmil 600 V
- THHN 750 kcmil 600 V
- THHN 800 kcmil 600 V
- THHN 900 kcmil 600 V
- THHN 1000 kcmil 600 V
THWN-2: equivalents in other countries
Shown for 1x3.31 600 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | no letters for this build | Close | Insulation 0.38 → 1 mm; Overall diameter 3.23 → 4.47 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
THWN-2 as the cable designer builds it, 12 AWG, 600 V
Overall diameter 3.2 mm, about 40 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.38 | 3.0 |
| Nylon jacket (polyamide) | Nylon (PA) | 0.10 | 3.2 |
THWN-2 on a drum
The smallest drum that passes every check, for 3.2 mm and about 40 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 14x10x5, wood NEMA reels (North America), Okonite | 13 of 21 | 22 kg |
| 1,000 m | NEMA 18x10x6, wood NEMA reels (North America), Okonite | 21 of 34 | 45 kg |
Barrel at least 20 × OD = 65 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: THWN-2
THWN-2 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with THWN-2
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.