SEU
SEU is a NEC / UL (USA) cable designation: SE = Service-entrance cable; U = Flat (oval) cable with a concentric bare neutral (reading by usage, UNVERIFIED); SEU = Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: UL 44 (edition 19): Thermoset-Insulated Wires and Cables; UL 854 (edition 12): Service-Entrance Cables. How the values are sourced
Worked reading of SEU 2/C 2 AWG, 600 V:
SEU: SE = Service-entrance cable; U = Flat (oval) cable with a concentric bare neutral (reading by usage, UNVERIFIED); SEU = Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 3382/C 2 AWG, 600 V: 2 cores, each aluminium 2 AWG (33.6 mm²); rated voltage 600 V
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
SE | Service-entrance cable |
U | Flat (oval) cable with a concentric bare neutral (reading by usage, UNVERIFIED) |
SEU | Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338 |
NEC Article 310 (US building wire, NFPA 70)
| Symbol | Meaning |
|---|---|
SE | Service Entrance |
U | Underground Use |
How to read a NEC Article 310 (US building wire, NFPA 70) cable code
What is SEU cable?
SEU: Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. Rating: 600 V, 90 C (XLPE) or 75 C (PVC). Standard: UL 854; NEC Article 338.
Two insulated phases under a helical bare neutral. A "6-6-6" size list counts the neutral as the third size.
Documents and pages the readings were taken from
SEU as the cable designer builds it, 2/C 2 AWG, 600 V
Flat, 23.7 × 14.6 mm (width × thickness), about 410 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 1.1 | 9.1 |
| Wire screen | Aluminium | 12 × 1.50 | 12.1 |
| Separation tape | Polyester | 0.10 | 12.3 |
| Sheath | PVC | 1.1 | 14.6 |
SEU on a drum
The smallest drum that passes every check, for 23.7 mm and about 410 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 40x24x17, wood NEMA reels (North America), American Wire Group, Okonite | 11 of 11 | 241–273 kg |
| 1,000 m | NEMA 50x32x23, wood NEMA reels (North America), American Wire Group | 12 of 13 | 514 kg |
Barrel at least 15 × OD = 355 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: SEU
SEU belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with SEU
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.