SEU

SEU is a NEC / UL (USA) cable designation: SE = Service-entrance cable; U = Flat (oval) cable with a concentric bare neutral (reading by usage, UNVERIFIED); SEU = Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: UL 44 (edition 19): Thermoset-Insulated Wires and Cables; UL 854 (edition 12): Service-Entrance Cables. How the values are sourced

Worked reading of SEU 2/C 2 AWG, 600 V:

  • SEU: SE = Service-entrance cable; U = Flat (oval) cable with a concentric bare neutral (reading by usage, UNVERIFIED); SEU = Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338
  • 2/C 2 AWG, 600 V: 2 cores, each aluminium 2 AWG (33.6 mm²); rated voltage 600 V

NEC / UL (USA)

SymbolMeaning
SEService-entrance cable
UFlat (oval) cable with a concentric bare neutral (reading by usage, UNVERIFIED)
SEUService-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338

NEC Article 310 (US building wire, NFPA 70)

SymbolMeaning
SEService Entrance
UUnderground Use

How to read a NEC Article 310 (US building wire, NFPA 70) cable code

What is SEU cable?

SEU: Service-entrance cable, style U (flat), with a concentric bare neutral, gray jacket. Rating: 600 V, 90 C (XLPE) or 75 C (PVC). Standard: UL 854; NEC Article 338.

Two insulated phases under a helical bare neutral. A "6-6-6" size list counts the neutral as the third size.

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

SEU as the cable designer builds it, 2/C 2 AWG, 600 V

Flat, 23.7 × 14.6 mm (width × thickness), about 410 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE1.19.1
Wire screenAluminium12 × 1.5012.1
Separation tapePolyester0.1012.3
SheathPVC1.114.6

SEU on a drum

The smallest drum that passes every check, for 23.7 mm and about 410 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 40x24x17, wood NEMA reels (North America), American Wire Group, Okonite11 of 11241–273 kg
1,000 mNEMA 50x32x23, wood NEMA reels (North America), American Wire Group12 of 13514 kg

Barrel at least 15 × OD = 355 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: SEU

SEU belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with SEU

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations

SEU