SER

SER is a NEC / UL (USA) cable designation: SE = Service-entrance cable; R = Round cable with separate neutral and ground (reading by usage, UNVERIFIED); SER = Service-entrance cable, style R (round), with a bare ground, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338.

4 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: UL 83 (edition 16): Thermoplastic-Insulated Wires and Cables; UL 44 (edition 19): Thermoset-Insulated Wires and Cables; UL 854 (edition 12): Service-Entrance Cables. How the values are sourced

Worked reading of SER 3/C 4/0 AWG, 600 V:

  • SER: SE = Service-entrance cable; R = Round cable with separate neutral and ground (reading by usage, UNVERIFIED); SER = Service-entrance cable, style R (round), with a bare ground, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338
  • 3/C 4/0 AWG, 600 V: 3 cores, each aluminium 4/0 AWG (107.2 mm²); rated voltage 600 V

NEC / UL (USA)

SymbolMeaning
SEService-entrance cable
RRound cable with separate neutral and ground (reading by usage, UNVERIFIED)
SERService-entrance cable, style R (round), with a bare ground, gray jacket. 600 V, 90 C (XLPE) or 75 C (PVC). UL 854; NEC Article 338

NEC Article 310 (US building wire, NFPA 70)

SymbolMeaning
SEService Entrance
RThermoset Insulation

How to read a NEC Article 310 (US building wire, NFPA 70) cable code

CEI-UNEL 35011 (Italy)

SymbolMeaning
SSector Shaped Stranded Conductor
EThermoplastic Polyethylene (PE) Compound
RPVC Compound (TI1/TI2 Quality, 70 °C)

How to read a CEI-UNEL 35011 (Italy) cable code

UNE (Spain: UNE 21123 / UNE 20434)

SymbolMeaning
SSilicone Rubber
EPolyethylene (PE)
RCross-Linked Polyethylene (XLPE)

How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code

What is SER cable?

SER: Service-entrance cable, style R (round), with a bare ground, gray jacket. Rating: 600 V, 90 C (XLPE) or 75 C (PVC). Standard: UL 854; NEC Article 338.

The "4-4-4-6" form lists one size per conductor: three insulated plus the smaller bare ground. Copper or aluminium.

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

SER as the cable designer builds it, 3/C 4/0 AWG, 600 V

Overall diameter 35.8 mm, about 1,400 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE1.414.9
Separation tapePolyester0.1034.3
SheathPVC0.7635.8

SER on a drum

The smallest drum that passes every check, for 35.8 mm and about 1,400 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 54x32x26, wood NEMA reels (North America), American Wire Group, Okonite9 of 9774–841 kg
1,000 mNEMA 68x38x28, wood NEMA reels (North America), American Wire Group12 of 131,650 kg

Barrel at least 15 × OD = 537 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: SER

SER belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²