NYSY

NYSY is a NTP (Peru) cable designation: S = Copper tape shield (reading UNVERIFIED); NYSY = NYSY: PVC insulated cable with copper tape shield and PVC sheath (reading UNVERIFIED). 0.6/1 kV UNVERIFIED. NTP-IEC 60502-1.

3 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of NYSY 1x240/25 3.6/6 kV:

  • NYSY: S = Copper tape shield (reading UNVERIFIED); NYSY = NYSY: PVC insulated cable with copper tape shield and PVC sheath (reading UNVERIFIED). 0.6/1 kV UNVERIFIED. NTP-IEC 60502-1
  • 1x240/25 3.6/6 kV: one core, copper 240 mm²; rated voltage 3.6/6 kV

Related cable types: NYSYL · NYY · NYSLY · NYBY · NYCY · NYRY

NTP (Peru)

SymbolMeaning
SCopper tape shield (reading UNVERIFIED)
NYSYNYSY: PVC insulated cable with copper tape shield and PVC sheath (reading UNVERIFIED). 0.6/1 kV UNVERIFIED. NTP-IEC 60502-1

DIN VDE 0271/0276 power cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC)
SCopper Screen (Wires, Or Wires And Tape); On Multi-Core Cables Over The Laid-Up Cores
YPolyvinyl Chloride (PVC)

How to read a DIN VDE 0271/0276 power cables (Germany) cable code

DIN VDE 0250 cords, control and special cables (Germany)

SymbolMeaning
NVDE Standard
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General
SBraiding Of Galvanised Steel Wires
YPolyvinyl Chloride (PVC); Control-Cable Key: Thermoplastics In General

How to read a DIN VDE 0250 cords, control and special cables (Germany) cable code

What is NYSY cable?

NYSY: PVC insulated cable with copper tape shield and PVC sheath (reading UNVERIFIED). Rating: 0.6/1 kV UNVERIFIED. Standard: NTP-IEC 60502-1.

Documents and pages the readings were taken from

NTP (Peru): how to read the cable type names

NYSY as the cable designer builds it, 1x240/25 3.6/6 kV

Overall diameter 33.6 mm, about 3,160 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6019.6
InsulationPVC3.426.4
Insulation screen (semicon)Semiconducting0.8028.0
Wire screenCopper65 × 0.7029.6
SheathPVC2.033.6

NYSY on a drum

The smallest drum that passes every check, for 33.6 mm and about 3,160 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 18 (1800 mm flange), wood KTG drums (Europe), Bayka, KTG6 of 111,921–1,993 kg
1,000 mKTG 18 (1800 mm flange), wood KTG drums (Europe), Bayka, KTG11 of 113,501–3,573 kg

Barrel at least 25 × OD = 840 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: NYSY

NYSY belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with NYSY

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NTP (Peru) designations

NYSY