MV-105
MV-105 is a NEC / UL (USA) cable designation: MV = Medium voltage; -105 = Conductor temperature rating 105 C (emergency 140 C, short circuit 250 C); MV-105 = Medium-voltage shielded power cable, 105 C. 2 kV to 35 kV, 105 C. UL 1072; NEC Article 311.
1 coding system recognises this code
Standard, worked reading and related types
Standards behind these values: UL 1072: Medium-Voltage Power Cables. How the values are sourced
Worked reading of MV-105 1/0 AWG, 15 kV 133 %:
MV-105: MV = Medium voltage; -105 = Conductor temperature rating 105 C (emergency 140 C, short circuit 250 C); MV-105 = Medium-voltage shielded power cable, 105 C. 2 kV to 35 kV, 105 C. UL 1072; NEC Article 3111/0 AWG, 15 kV 133 %: one core, copper 1/0 AWG (53.5 mm²); rated voltage 15 kV 133 %
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
MV | Medium voltage |
-105 | Conductor temperature rating 105 C (emergency 140 C, short circuit 250 C) |
MV-105 | Medium-voltage shielded power cable, 105 C. 2 kV to 35 kV, 105 C. UL 1072; NEC Article 311 |
What is MV-105 cable?
MV-105: Medium-voltage shielded power cable, 105 C. Rating: 2 kV to 35 kV, 105 C. Standard: UL 1072; NEC Article 311.
Built from one 15 kV EPR 133 percent page: conductor and insulation shields are semiconducting XLPE, tape shield is tinned copper. 105 C normal, 140 C emergency, 250 C short circuit: AEIC CS8-20 Table D-2 (ANSI/ICEA S-94-649 and S-97-682 Table 4-1, class III XLPE, TRXLPE and EPR; standard). A 5 mil copper tape and a PVC jacket: Okonite (sheet 2-9), Southwire (SPEC 46302) and Prysmian (SPEC 6355) agree. Copper conductors also exist ("CU" switches the metal).
Documents and pages the readings were taken from
MV-105 as the cable designer builds it, 1/0 AWG, 15 kV 133 %
Overall diameter 27.4 mm, about 1,240 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.48 | 10.2 |
| Insulation | EPR | 5.6 | 21.3 |
| Insulation screen (semicon) | Semiconducting | 0.76 | 22.9 |
| Tape screen | Copper | 0.25 | 23.4 |
| Sheath | PVC | 2.0 | 27.4 |
MV-105 on a drum
The smallest drum that passes every check, for 27.4 mm and about 1,240 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite | 7 of 13 | 705–770 kg |
| 1,000 m | NEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite | 12 of 13 | 1,325–1,390 kg |
Barrel at least 25 × OD = 686 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: MV-105
MV-105 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with MV-105
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.