MV-105

MV-105 is a NEC / UL (USA) cable designation: MV = Medium voltage; -105 = Conductor temperature rating 105 C (emergency 140 C, short circuit 250 C); MV-105 = Medium-voltage shielded power cable, 105 C. 2 kV to 35 kV, 105 C. UL 1072; NEC Article 311.

1 coding system recognises this code

Standard, worked reading and related types

Standards behind these values: UL 1072: Medium-Voltage Power Cables. How the values are sourced

Worked reading of MV-105 1/0 AWG, 15 kV 133 %:

  • MV-105: MV = Medium voltage; -105 = Conductor temperature rating 105 C (emergency 140 C, short circuit 250 C); MV-105 = Medium-voltage shielded power cable, 105 C. 2 kV to 35 kV, 105 C. UL 1072; NEC Article 311
  • 1/0 AWG, 15 kV 133 %: one core, copper 1/0 AWG (53.5 mm²); rated voltage 15 kV 133 %

NEC / UL (USA)

SymbolMeaning
MVMedium voltage
-105Conductor temperature rating 105 C (emergency 140 C, short circuit 250 C)
MV-105Medium-voltage shielded power cable, 105 C. 2 kV to 35 kV, 105 C. UL 1072; NEC Article 311

What is MV-105 cable?

MV-105: Medium-voltage shielded power cable, 105 C. Rating: 2 kV to 35 kV, 105 C. Standard: UL 1072; NEC Article 311.

Built from one 15 kV EPR 133 percent page: conductor and insulation shields are semiconducting XLPE, tape shield is tinned copper. 105 C normal, 140 C emergency, 250 C short circuit: AEIC CS8-20 Table D-2 (ANSI/ICEA S-94-649 and S-97-682 Table 4-1, class III XLPE, TRXLPE and EPR; standard). A 5 mil copper tape and a PVC jacket: Okonite (sheet 2-9), Southwire (SPEC 46302) and Prysmian (SPEC 6355) agree. Copper conductors also exist ("CU" switches the metal).

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

MV-105 as the cable designer builds it, 1/0 AWG, 15 kV 133 %

Overall diameter 27.4 mm, about 1,240 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.4810.2
InsulationEPR5.621.3
Insulation screen (semicon)Semiconducting0.7622.9
Tape screenCopper0.2523.4
SheathPVC2.027.4

MV-105 on a drum

The smallest drum that passes every check, for 27.4 mm and about 1,240 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite7 of 13705–770 kg
1,000 mNEMA 58x32x28, wood NEMA reels (North America), American Wire Group, Okonite12 of 131,325–1,390 kg

Barrel at least 25 × OD = 686 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: MV-105

MV-105 belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with MV-105

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations

MV-105