CL2X
CL2X is a NEC / UL (USA) cable designation: CL = Class 2 or 3 power-limited circuit cable; 2 = Class 2 circuit; X = Limited use (VW-1 vertical flame test); CL2X = Class 2 remote-control and signalling cable, limited use. Class 2 power-limited, no voltage rating (UL 13 1.2). UL 13; NEC (2026) Article 722.
1 coding system recognises this code
Standard, worked reading and related types
Worked reading of CL2X 2/C 18 AWG, 150 V:
CL2X: CL = Class 2 or 3 power-limited circuit cable; 2 = Class 2 circuit; X = Limited use (VW-1 vertical flame test); CL2X = Class 2 remote-control and signalling cable, limited use. Class 2 power-limited, no voltage rating (UL 13 1.2). UL 13; NEC (2026) Article 7222/C 18 AWG, 150 V: 2 cores, each copper 18 AWG (0.8 mm²); rated voltage 150 V
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
CL | Class 2 or 3 power-limited circuit cable |
2 | Class 2 circuit |
X | Limited use (VW-1 vertical flame test) |
CL2X | Class 2 remote-control and signalling cable, limited use. Class 2 power-limited, no voltage rating (UL 13 1.2). UL 13; NEC (2026) Article 722 |
What is CL2X cable?
CL2X: Class 2 remote-control and signalling cable, limited use. Rating: Class 2 power-limited, no voltage rating (UL 13 1.2). Standard: UL 13; NEC (2026) Article 722.
X read in UL 13 ed. 4 (2015, revised 2025-06-12) 47.1(a)(1) (limited use, VW-1, not marked VW-1), seen standard; UL 13 1.9 quotes the NEC limits: an exposed length of 10 ft (3.05 m), and in dwellings a cable under 0.25 in (6.35 mm). The designer builds the unjacketed twisted cable of Table 12.1 (walls Tables 7.4 and 7.5).
Documents and pages the readings were taken from
Not equivalent, because
IEC 60332-1-2 ≠ VW-1 (UL 2556 FV-2) / FT1
Not equivalent, because The flame, the number of flame applications and the pass criterion differ: a cable that passes one has not shown that it passes the other.
IEC 60332-1-2
- One 1 kW flame on a single vertical cable, applied once for a time set by the cable diameter. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
- Pass: the char ends at least 50 mm below the top clamp and no lower than 540 mm below it. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
- CPR class Eca uses the same test: the flame stops within 425 mm. Sources: EN 13501-6 draft (BSI FSH/21_11_0073, undated, before the published EN 13501-6:2014), Table 1 (read in a draft)
VW-1 (UL 2556 FV-2) / FT1
- 5 flame applications of 15 s each. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)
- Judged by a paper indicator flag above the flame and cotton below the cable; their limits are not held here. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)
CL2X as the cable designer builds it, 2/C 18 AWG, 150 V
Overall diameter 4.4 mm, about 20 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.51 | 2.2 |
CL2X on a drum
The smallest drum that passes every check, for 4.4 mm and about 20 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 14x10x5, wood NEMA reels (North America), Okonite | 16 of 16 | 12 kg |
| 1,000 m | NEMA 18x10x6, wood NEMA reels (North America), Okonite | 24 of 25 | 25 kg |
Barrel at least 15 × OD = 66 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: CL2X
CL2X belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²