CL3X

CL3X is a NEC / UL (USA) cable designation: CL = Class 2 or 3 power-limited circuit cable; 3 = Class 3 circuit; X = Limited use (VW-1 vertical flame test); CL3X = Class 3 remote-control and signalling cable, limited use. 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked). UL 13; NEC (2026) Article 722.

1 coding system recognises this code

Standard, worked reading and related types

Worked reading of CL3X 2/C 18 AWG, 300 V:

  • CL3X: CL = Class 2 or 3 power-limited circuit cable; 3 = Class 3 circuit; X = Limited use (VW-1 vertical flame test); CL3X = Class 3 remote-control and signalling cable, limited use. 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked). UL 13; NEC (2026) Article 722
  • 2/C 18 AWG, 300 V: 2 cores, each copper 18 AWG (0.8 mm²); rated voltage 300 V

Related cable types: CL3P · CL2X · CL3 · CL3R

NEC / UL (USA)

SymbolMeaning
CLClass 2 or 3 power-limited circuit cable
3Class 3 circuit
XLimited use (VW-1 vertical flame test)
CL3XClass 3 remote-control and signalling cable, limited use. 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked). UL 13; NEC (2026) Article 722

What is CL3X cable?

CL3X: Class 3 remote-control and signalling cable, limited use. Rating: 300 V, Class 3 power-limited (UL 13 1.2: rated 300 V, not so marked). Standard: UL 13; NEC (2026) Article 722.

X read in UL 13 ed. 4 (2015, revised 2025-06-12) 47.1(a)(1) (limited use, VW-1, not marked VW-1), seen standard; UL 13 1.9 quotes the NEC limits: an exposed length of 10 ft (3.05 m), and in dwellings a cable under 0.25 in (6.35 mm). The designer builds the unjacketed twisted cable of Table 12.1 (walls Tables 7.4 and 7.5).

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

Not equivalent, because

IEC 60332-1-2 ≠ VW-1 (UL 2556 FV-2) / FT1

Not equivalent, because The flame, the number of flame applications and the pass criterion differ: a cable that passes one has not shown that it passes the other.

IEC 60332-1-2

  • One 1 kW flame on a single vertical cable, applied once for a time set by the cable diameter. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
  • Pass: the char ends at least 50 mm below the top clamp and no lower than 540 mm below it. Sources: IEC 60332-1-2:2004+AMD1:2015 (edition 1.1), Table 1 p. 7 (flame time by diameter), Annex A p. 11 (recommended pass) (read in the standard)
  • CPR class Eca uses the same test: the flame stops within 425 mm. Sources: EN 13501-6 draft (BSI FSH/21_11_0073, undated, before the published EN 13501-6:2014), Table 1 (read in a draft)

VW-1 (UL 2556 FV-2) / FT1

  • 5 flame applications of 15 s each. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)
  • Judged by a paper indicator flag above the flame and cotton below the cable; their limits are not held here. Sources: UL 1581, 4th ed. revised to 2013-01-30, clause 1080.1 (the VW-1 method, now UL 2556 FV-2) (read in the standard)

All the comparisons →

CL3X as the cable designer builds it, 2/C 18 AWG, 300 V

Overall diameter 4.4 mm, about 20 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.512.2

CL3X on a drum

The smallest drum that passes every check, for 4.4 mm and about 20 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 14x10x5, wood NEMA reels (North America), Okonite16 of 1612 kg
1,000 mNEMA 18x10x6, wood NEMA reels (North America), Okonite24 of 2525 kg

Barrel at least 15 × OD = 66 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: CL3X

CL3X belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²