CL2P

CL2P is a NEC / UL (USA) cable designation: CL = Class 2 or 3 power-limited circuit cable; 2 = Class 2 circuit; P = Plenum (NFPA 262 tunnel test); CL2P = Class 2 remote-control and signalling cable, plenum. Class 2 power-limited, no voltage rating (UL 13 1.2). UL 13; NEC (2026) Article 722.

1 coding system recognises this code

Standard, worked reading and related types

Worked reading of CL2P 2/C 18 AWG, 150 V:

  • CL2P: CL = Class 2 or 3 power-limited circuit cable; 2 = Class 2 circuit; P = Plenum (NFPA 262 tunnel test); CL2P = Class 2 remote-control and signalling cable, plenum. Class 2 power-limited, no voltage rating (UL 13 1.2). UL 13; NEC (2026) Article 722
  • 2/C 18 AWG, 150 V: 2 cores, each copper 18 AWG (0.8 mm²); rated voltage 150 V

Related cable types: CL3P · CL2 · CL2R · CL2X

NEC / UL (USA)

SymbolMeaning
CLClass 2 or 3 power-limited circuit cable
2Class 2 circuit
PPlenum (NFPA 262 tunnel test)
CL2PClass 2 remote-control and signalling cable, plenum. Class 2 power-limited, no voltage rating (UL 13 1.2). UL 13; NEC (2026) Article 722

What is CL2P cable?

CL2P: Class 2 remote-control and signalling cable, plenum. Rating: Class 2 power-limited, no voltage rating (UL 13 1.2). Standard: UL 13; NEC (2026) Article 722.

P, R and X read in UL 13 ed. 4 (2015, revised 2025-06-12) 47.1(a)(1), seen standard: P plenum (NFPA 262), R riser (UL 1666), plain the vertical tray test, X limited use (VW-1); each rung may replace the ones below it (a CL2P for a CL2R, CL2 or CL2X).

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

Not equivalent, because

CPR B2ca / Cca (EN 50399) ≠ NFPA 262 (CMP, CL2P, FPLP, OFNP, FT6)

Not equivalent, because Different apparatus (a horizontal tunnel with forced air against a vertical ladder) and different measures (flame travel and optical density against heat release, flame spread and smoke production).

CPR B2ca / Cca (EN 50399)

  • Cables on a vertical ladder. B2ca: flame spread at most 1.5 m, total heat 15 MJ, peak heat release 30 kW, FIGRA 150 W/s. Sources: EN 13501-6 draft (BSI FSH/21_11_0073, undated, before the published EN 13501-6:2014), Table 1 (read in a draft)
  • Cca: flame spread at most 2 m, total heat 30 MJ, peak heat release 60 kW, FIGRA 300 W/s. Sources: EN 13501-6 draft (BSI FSH/21_11_0073, undated, before the published EN 13501-6:2014), Table 1 (read in a draft)
  • Smoke class s1: total smoke at most 50 m², peak rate at most 0.25 m²/s. Sources: EN 13501-6 draft (BSI FSH/21_11_0073, undated, before the published EN 13501-6:2014), Table 1 notes (2) to (7), p. 21 (read in a draft)

NFPA 262 (CMP, CL2P, FPLP, OFNP, FT6)

All the comparisons →

CL2P as the cable designer builds it, 2/C 18 AWG, 150 V

Overall diameter 3.9 mm, about 20 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.231.6
SheathPVC0.333.9

CL2P on a drum

The smallest drum that passes every check, for 3.9 mm and about 20 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 14x10x5, wood NEMA reels (North America), Okonite15 of 1712 kg
1,000 mNEMA 18x10x6, wood NEMA reels (North America), Okonite23 of 2825 kg

Barrel at least 15 × OD = 59 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: CL2P

CL2P belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with CL2P

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations

CL2P