Project requirements · Environment

UV and sunlight resistance

The outer sheath keeps its mechanical properties after long exposure to sunlight outdoors.

Open in the designer with this requirement

Constructions that meet it

  • UV-stable (carbon black): changes no layer: a property of the sheath compound. Black sheath with dispersed carbon black (PE: about 2.5 %) (black PE (or PVC) with carbon black). Drawbacks: Cheapest; forces black colour.
  • UV-stable (UV stabiliser in the compound): changes no layer: a property of the sheath compound. UV stabiliser package in a coloured or halogen-free sheath compound (sheath compound + UV stabiliser). Drawbacks: Needs a test to prove it; some colours fade (Lapp allows colour change).
  • Hard polyamide (nylon) jacket over the sheath: changes the cable's layers. UV-stabilised nylon jacket over the sheath (PA, UV stabilised). Drawbacks: When a nylon jacket is there anyway (termite).

Writing a tender? Pro writes this requirement into your specification, ready to copy. Open in the designer with this requirement · See Pro

Tests

  • EN 50289-4-17:2015: UV resistance of sheaths: xenon arc, fluorescent lamp or mercury vapour lamp. Pass: set by the product standard; exempt when UV resistance comes from 2.5 % carbon black dispersed per EN 50290-2-24
  • EN 50618 Annex E (PV cables): 720 h (360 cycles), UV light per EN 50289-4-17 method A. Pass: tensile strength and elongation at break after ageing (limits not found in the maker sheet)
  • UL 1581 section 1200: 720 h carbon-arc or xenon-arc exposure. Pass: 80 % retention of tensile strength and elongation
  • EN ISO 4892-2 method A: xenon arc weathering. Pass: maker's ('change of colour allowed', Lapp)
  • HD 605 S2 / VDE 0276-605: weathering test cited by Lapp ÖLFLEX ROBUST 200. Pass: not found
  • IEC 60502-2:2014 clause 19.17: carbon black content of black PE oversheaths (IEC 60811-605). Pass: not read (clause listed in the contents)
  • ISO 4892-3: fluorescent UV, cited for UV and ozone by Draka NEK 606 cables. Pass: not found

In the base standard for some designs: IEC 60502-2:2014 clause 19.17, carbon black content of black PE oversheaths (IEC 60811-605).

How specifications state it

Usually 'UV resistant' or 'sunlight resistant' with one of the tests above; black PE with carbon black is often accepted without a test.

Where it is asked for

  • PV plants
  • cable trays outdoors
  • aerial and facade runs
  • offshore topsides
  • North American tray cable marked 'Sunlight Resistant'

Sources

More requirements in this group