Project requirements · Environment
High ambient or conductor temperature
The cable runs in hot surroundings or at a conductor temperature above the base standard's 70 or 90 °C.
Open in the designer with this requirement
Constructions that meet it
- HEPR / EPR insulation: changes no layer: a property of the insulation compound. HEPR / EPR insulation (HEPR, EPR). Drawbacks: Rubber insulation for 90 °C and above; MV-105 rating in North America.
- XLPE rated 105 °C (MV-105): changes no layer: a property of the insulation compound. TR-XLPE or XLPE at 105 °C (MV-105) (XLPE grade). Drawbacks: LS Cable: 105 °C normal, 140 °C emergency with XLPE jacket.
- Silicone rubber insulation and sheath: changes no layer: a property of the insulation compound. Silicone rubber insulation and sheath (silicone (SiHF)). Drawbacks: Helukabel SiHF: -60 to +180 °C fixed; mechanical properties fall above about 90 to 100 °C without air (Lapp, dealer note).
- Cross-linked halogen-free compound rated 120 °C: changes no layer: a property of the insulation compound. Cross-linked halogen-free compounds rated 120 °C (cross-linked polyolefin). Drawbacks: EN 50618 PV cables.
Writing a tender? Pro writes this requirement into your specification, ready to copy. Open in the designer with this requirement · See Pro
Tests
- IEC 60216-2: thermal endurance (Lapp PV cable: 120 °C conductor). Pass: maker's endurance figure
- EN 50618 Table 2 / EN 60068-2-78: damp heat 1000 h at 90 °C and 85 % RH. Pass: maker sheet does not give the limit
- Product standard ageing tests: air oven ageing at the class temperature. Pass: set per material in the product standard
How specifications state it
Specified as a maximum conductor temperature (90, 105, 120, 180 °C) or an ambient, proven by the insulation material class.
Where it is asked for
- steel, glass and foundry plants
- boiler houses
- engine rooms
- PV arrays
- near furnaces and ovens
Sources
- Lapp H1Z2Z2-K datasheet (-40 to +120 °C conductor per IEC 60216-2; damp heat in the German sheet) (maker's catalogue)
- LS Cable USA, Spec U15BTX TR-XLPE MV-105 datasheet (105 / 140 / 250 °C) (maker's catalogue)
- Helukabel SiHF shop page M22989 (-60 to +180 °C fixed, EN 50525-2-83) (quoted by others)
- Lapp ÖLFLEX HEAT 180 SiHF product page (up to +180 °C; ventilation note) (quoted by others)