YKXSEKTMY
YKXSEKTMY on PN (Poland)-järjestelmän kaapelin tyyppimerkintä: Y = PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names; K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; ektm = Copper tape screen; y = PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC); YKXSEKTMY = YKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.
1 merkintäjärjestelmä tunnistaa tämän merkinnän
PN (Poland)
| Symboli | Merkitys |
|---|---|
Y | PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names |
K | kabel: power cable family (not a copper letter) |
XS | Cross-linked polyethylene (XLPE) insulation, replaces the final Y |
ektm | Copper tape screen |
y | PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC) |
YKXSEKTMY | YKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1 |
Palokäyttäytyminen (EU:n rakennustuoteasetus, CPR)
Palamista hidastava (y). Eca-luokan taustalla oleva yksittäisen kaapelin koe on EN 60332-1-2 (liekki sammuu 425 mm:n sisällä). Nipussa olevat kaapelit koestetaan standardin IEC 60332-3-24 luokan C mukaan (1,5 l/m, 20 min, hiiltyminen enintään 2,5 m); se ei ole CPR-luokan koe, luokkien B1ca–Dca CPR-koe on EN 50399.
CPR-luokan ilmoittaa valmistaja suoritustasoilmoituksessaan ja painaa sen vaippaan (EN 50575 kohta 7). Tämä purkutyökalu ei määritä luokkaa. Mitä CPR-luokat tarkoittavat →
Lähteet: EN 13501-6 -luonnos ja FprEN 50575:2014 -loppuluonnos (luonnokset, eivät julkaistut tekstit); IEC 60332-3-24:2000+A1:2008; EN 13501-3 A2 -luonnos.