YKXSEKTMY
YKXSEKTMY er en kabelbetegnelse efter PN (Poland): Y = PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names; K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; ektm = Copper tape screen; y = PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC); YKXSEKTMY = YKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.
1 kodesystem genkender denne betegnelse
PN (Poland)
| Symbol | Betydning |
|---|---|
Y | PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names |
K | kabel: power cable family (not a copper letter) |
XS | Cross-linked polyethylene (XLPE) insulation, replaces the final Y |
ektm | Copper tape screen |
y | PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC) |
YKXSEKTMY | YKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1 |
Brandegenskaber (EU-byggevareforordningen, CPR)
Flammehæmmende (y). Enkeltkabelprøvningen bag klasse Eca er EN 60332-1-2 (flammen slukker inden for 425 mm). Kabler i bundt prøves efter IEC 60332-3-24 kategori C (1,5 l/m, 20 min, forkulning højst 2,5 m); det er ikke en prøvning for en CPR-klasse, CPR-prøvningen for B1ca til Dca er EN 50399.
En CPR-klasse deklareres af producenten i ydeevnedeklarationen og trykkes på kappen (EN 50575 pkt. 7). Denne afkoder tildeler ingen klasse. Hvad CPR-klasserne betyder →
Kilder: udkast til EN 13501-6 og slutudkast FprEN 50575:2014 (udkast, ikke de offentliggjorte tekster); IEC 60332-3-24:2000+A1:2008; udkast til EN 13501-3 A2.