YKXSEKTMY

YKXSEKTMY er en kabelbetegnelse etter PN (Poland): Y = PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names; K = kabel: power cable family (not a copper letter); XS = Cross-linked polyethylene (XLPE) insulation, replaces the final Y; ektm = Copper tape screen; y = PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC); YKXSEKTMY = YKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1.

1 kodesystem gjenkjenner denne betegnelsen

PN (Poland)

SymbolBetydning
YPVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names
Kkabel: power cable family (not a copper letter)
XSCross-linked polyethylene (XLPE) insulation, replaces the final Y
ektmCopper tape screen
yPVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC)
YKXSEKTMYYKXSektmy: YKXS (XLPE) with a copper tape screen (ektm) and a PVC oversheath, 0,6/1 kV. 0,6/1 kV. PN-HD 603 S1:2006/A3:2009; IEC 60502-1

Brannegenskaper (EU-forordningen for byggevarer, CPR)

  • Flammehemmende (y). Enkeltkabelprøvingen bak klasse Eca er EN 60332-1-2 (flammen slukner innen 425 mm). Kabler i bunt prøves etter IEC 60332-3-24 kategori C (1,5 l/m, 20 min, forkulling høyst 2,5 m); det er ikke en prøving for en CPR-klasse, CPR-prøvingen for B1ca til Dca er EN 50399.

En CPR-klasse erklæres av produsenten i ytelseserklæringen og trykkes på kappen (EN 50575 pkt. 7). Denne dekoderen tildeler ingen klasse. Hva CPR-klassene betyr →

Kilder: utkast til EN 13501-6 og sluttutkast FprEN 50575:2014 (utkast, ikke de publiserte tekstene); IEC 60332-3-24:2000+A1:2008; utkast til EN 13501-3 A2.