TECK90 dimensions

Nominal calculation, not one manufacturer's datasheet. The conductors are NEC Chapter 9 Table 8; the RW90 walls, the bond, both jackets and the armour band are the values seven makers print or give through their diameters, because CSA C22.2 No. 131 was not read. Check the datasheet before you specify or order.

Each row is one TECK90 size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What TECK90 means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 24 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
3C 14 AWG600 V0.7618.3300
3C 12 AWG600 V0.7619.0350
3C 10 AWG600 V0.7620.4450
3C 14 AWG1000 V1.1419.6340
3C 12 AWG1000 V1.1420.5390
3C 10 AWG1000 V1.1421.6480
3C 8 AWG1000 V1.1424.6670
3C 6 AWG1000 V1.5228.2940
3C 4 AWG1000 V1.5231.81,280
3C 3 AWG1000 V1.5233.31,520
3C 2 AWG1000 V1.5235.01,760
3C 1 AWG1000 V2.0339.32,160
3C 1/0 AWG1000 V2.0341.52,530
3C 2/0 AWG1000 V2.0343.82,980
3C 3/0 AWG1000 V2.0346.63,620
3C 4/0 AWG1000 V2.0349.74,330
3C 250 kcmil1000 V2.2954.85,190
3C 300 kcmil1000 V2.2957.75,980
3C 350 kcmil1000 V2.2960.56,820
3C 400 kcmil1000 V2.2962.97,620
3C 500 kcmil1000 V2.2967.59,160
3C 600 kcmil1000 V2.2971.710,780
3C 750 kcmil1000 V2.2977.313,080
3C 1000 kcmil1000 V2.2986.917,250