TECK90 3C 2 AWG 1000 V

Nominal calculation, not one manufacturer's datasheet. The conductors are NEC Chapter 9 Table 8; the RW90 walls, the bond, both jackets and the armour band are the values seven makers print or give through their diameters, because CSA C22.2 No. 131 was not read. Check the datasheet before you specify or order.

By NEC Table 8 and the catalogued walls, TECK90 3C 2 AWG 1000 V comes to an overall diameter of about 35.0 mm and a weight of about 1,760 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorCopper 2 AWG (33.6 mm²), Ø 7.2 mmcompressed Class B: ICEA S-94-649 Table C-4 as Elastimold prints it; below 2 AWG NEC Table 8 x 0.97 (its note)
InsulationXLPE 1.52 mmTECK90 RW90 XLPE insulation: 30 mil at 600 V; 45, 60, 80, 90 mil at 1000 V, as six makers print it (CSA C22.2 No. 131 not read)
Diameter over insulation10.2 mm
Core diameter10.2 mm
Overall diameter35.0 mm
Weight (approximate)1,760 kg/km

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationXLPE1.5210.2 (on each core)TECK90 RW90 XLPE insulation: 30 mil at 600 V; 45, 60, 80, 90 mil at 1000 V, as six makers print it (CSA C22.2 No. 131 not read)maker catalogue value, standard text not read
2Separation tapePolyester0.1022.3typical polyester tapetypical value, no rule
3Inner covering / beddingPVC2.0326.3TECK90 PVC inner jacket: 45, 60, 80, 110, 140 mil, as United Wire & Cable and Nexans print itmaker catalogue value, standard text not read
4Interlocked armourAluminium3.0532.4TECK90 interlocked aluminium armour, radial band 0.120 in (3.05 mm): derived from five makers' diameters over the armour and over the inner jacket; the strip is not printedmaker catalogue value, standard text not read
5SheathPVC1.2735.0TECK90 PVC outer jacket 50 mil: the median derived from seven makers' diameters (Southwire prints 45 to 80 mil)maker catalogue value, standard text not read

TECK90 is the CSA C22.2 No. 131 armoured cable: RW90 XLPE conductors and a bare copper bond in an outer interstice, a binder tape, a PVC inner jacket, interlocked aluminium armour and a PVC outer jacket. Checked against United Wire & Cable, Prysmian, Texcan, Nexans Canada, Shawflex, Northern Cables and Southwire: research/designer-americas/mc-teck.md in the site repository.

Materials in this cable: Copper, Aluminium, XLPE, PVC

Weight, by part

Conductors1,060 kg/km
Metal screens and armour150 kg/km
Insulation, semicon, tapes, fillers and sheaths550 kg/km
Total1,760 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

Laying, sizes and datasheet: TECK90 3C 2 AWG 1000 V

TECK90 3C 2 AWG 1000 V belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Who makes or stocks this cable?

TECK90