N2XY dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of N2XY, sized by the IEC rules the designer uses. Open a row for every layer and its source. What N2XY means, letter by letter.

Low voltage 0.6/1 kV · 26 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
4x1.50.6/1 kV0.712.3200
4x2.50.6/1 kV0.713.3250
4x40.6/1 kV0.714.4330
4x60.6/1 kV0.715.7420
4x100.6/1 kV0.717.6600
4x160.6/1 kV0.720.8890
4x250.6/1 kV0.924.61,320
4x350.6/1 kV0.927.01,740
3x1.50.6/1 kV0.711.6170
3x2.50.6/1 kV0.712.5210
3x40.6/1 kV0.713.5270
3x60.6/1 kV0.714.6340
3x100.6/1 kV0.716.3490
5x1.50.6/1 kV0.713.1230
5x2.50.6/1 kV0.714.2290
5x40.6/1 kV0.715.5380
5x60.6/1 kV0.716.8500
5x100.6/1 kV0.719.0720
1x500.6/1 kV1.013.0550
1x700.6/1 kV1.114.8750
1x950.6/1 kV1.116.71,010
1x1200.6/1 kV1.218.31,250
1x1500.6/1 kV1.420.31,560
1x1850.6/1 kV1.622.51,910
1x2400.6/1 kV1.725.22,460
1x3000.6/1 kV1.827.93,050