N2XY 5x4 RE 0,6/1 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, N2XY 5x4 RE 0,6/1 kV comes to an overall diameter of about 15.5 mm and a weight of about 380 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

Main dimensions

ConductorCopper 4 mm² RE, Ø 2.3 mmsolid, from the nominal section (IEC 60228 class 1)
InsulationXLPE 0.7 mmIEC 60502-1:2004 Tables 5-7, nominal insulation thickness
Diameter over insulation3.7 mm
Core diameter3.7 mm
Overall diameter15.5 mm
Weight (approximate)380 kg/km

Round conductors (IEC 60228 class 2 compacted; class 1 solid up to 10 mm²).

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationXLPE0.73.7 (on each core)IEC 60502-1:2004 Tables 5-7, nominal insulation thicknessas manufacturers publish it, table not read
2FillerPPfills the space between the cores9.9
3Inner covering / beddingPVC1.011.9IEC 60502 Table 8, extruded inner covering by the fictitious diameter over the laid-up cores (Annex A)read in the standard
4SheathPVC1.815.5IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Low voltage insulation (IEC 60502-1) is as manufacturers publish it; the table itself was not read. Sources and page numbers: research/mv-dimensions in the site repository.

Weight, by part

Conductors180 kg/km
Metal screens and armour0 kg/km
Insulation, semicon, tapes, fillers and sheaths200 kg/km
Total380 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).