IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of NAYY, sized by the IEC rules the designer uses. Open a row for every layer and its source. What NAYY means, letter by letter.

Low voltage 0.6/1 kV · 8 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
1x500.6/1 kV1.413.8280
1x700.6/1 kV1.415.4350
1x950.6/1 kV1.617.7470
1x1200.6/1 kV1.619.1560
1x1500.6/1 kV1.821.2690
1x1850.6/1 kV2.023.5840
1x2400.6/1 kV2.226.41,070
1x3000.6/1 kV2.429.31,320

Cable dimensions