NAYY 4x150 SE 0,6/1 kV

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

By the IEC construction rules, NAYY 4x150 SE 0,6/1 kV comes to an overall diameter of about 43.3 mm and a weight of about 2,930 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorAluminium 150 mm² SE, Ø 14.3 mmHD 603 3-G Table 1 (p. 3-G-20)
InsulationPVC 1.8 mmIEC 60502-1:2004 Tables 5-7, nominal insulation thickness
Diameter over insulation17.9 mm
Core diameter17.9 mm
Overall diameter43.3 mm
Weight (approximate)2,930 kg/km

Sector-shaped conductors (SM stranded, SE solid) to HD 603 Part 3 Section G, Appendix Tables 1 and 2. The diameter given is that of the circle with the sector's perimeter, on which the core layers are added.

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationPVC1.817.9 (on each core)IEC 60502-1:2004 Tables 5-7, nominal insulation thicknessas manufacturers publish it, table not read
2FillerPPfills the space between the cores35.5
3Inner covering / beddingPVC1.438.3IEC 60502 Table 8, extruded inner covering by the fictitious diameter over the laid-up cores (Annex A)read in the standard
4SheathPVC2.543.3IEC 60502 clause 13 / 14.3, oversheath: 0.035 D + 1.0 mm, D the fictitious diameter (Annex A)read in the standard

Diameters add up the nominal layers. Where IEC 60502 sizes a layer by the fictitious diameter of its Annex A, the calculated diameter is used instead, which can move a value one step. Low voltage insulation (IEC 60502-1) is as manufacturers publish it; the table itself was not read.

Materials in this cable: Aluminium, PVC

Weight, by part

Conductors1,650 kg/km
Metal screens and armour0 kg/km
Insulation, semicon, tapes, fillers and sheaths1,270 kg/km
Total2,930 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

NAYY 4x150 SE 0,6/1 kV: equivalents in other countries

Shown for 4x150 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
International (IEC)IEC 60502Al/PVC/PVC 4x150 0,6/1 kV (to IEC 60502-1)Equivalentevery value the same
IndiaIS 1554 (Part 1)AYY 4x150 1100 V (the code letters of IS 1554 (Part 1):1988 cl. 17.3)Closerated 0.635/1.1 kV (same Um 1.2 kV); conductor SE → RM; Inner covering / bedding 1.4 → 0.5 mm; Sheath 2.5 → 2.6 mm; this cable as built misses 1 of its rules

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

Laying, sizes and datasheet: NAYY 4x150 SE 0,6/1 kV

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 227 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 2.5 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 3, p. 12; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

NAYY 4x150 SE 0,6/1 kV belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.