NYY dimensions

IEC nominal calculation, not manufacturer data. The thicknesses are the nominal values of the construction standards, added up layer by layer. A manufacturer's cable of the same name can differ by a few millimetres and by 10 to 20 % in weight: always check its datasheet before you specify, order or lay a cable.

Each row is one construction of NYY, sized by the IEC rules the designer uses. Open a row for every layer and its source. What NYY means, letter by letter.

Low voltage 0.6/1 kV · 26 sizes

SizeVoltage U0/UInsulation mmOverall diameter mmWeight (approximate) kg/km
4x1.50.6/1 kV0.812.8220
4x2.50.6/1 kV0.813.8280
4x40.6/1 kV1.015.9380
4x60.6/1 kV1.017.1480
4x100.6/1 kV1.019.0680
4x160.6/1 kV1.022.3980
4x250.6/1 kV1.226.01,430
4x350.6/1 kV1.228.41,860
3x1.50.6/1 kV0.812.0190
3x2.50.6/1 kV0.812.9230
3x40.6/1 kV1.014.8320
3x60.6/1 kV1.015.9400
3x100.6/1 kV1.017.6540
5x1.50.6/1 kV0.813.7250
5x2.50.6/1 kV0.814.7320
5x40.6/1 kV1.017.1450
5x60.6/1 kV1.018.5580
5x100.6/1 kV1.020.6810
1x500.6/1 kV1.413.8590
1x700.6/1 kV1.415.4790
1x950.6/1 kV1.617.71,070
1x1200.6/1 kV1.619.11,310
1x1500.6/1 kV1.821.21,640
1x1850.6/1 kV2.023.52,010
1x2400.6/1 kV2.226.42,580
1x3000.6/1 kV2.429.33,210

Cable dimensions