YXC8V-R

YXC8V-R is a TS 621 / TSE (Turkey) cable designation: Y = Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212); X = Cross-Linked Polyethylene (XLPE) Insulation; C8 = Copper Wire Screen Over Each Core; V = Polyvinyl Chloride (PVC); -R = Round Stranded Conductor (Class 2).

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of YXC8V-R 1x95/16 12/20 kV:

  • YXC8V-R: Y = Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212); X = Cross-Linked Polyethylene (XLPE) Insulation; C8 = Copper Wire Screen Over Each Core; V = Polyvinyl Chloride (PVC); -R = Round Stranded Conductor (Class 2)
  • 1x95/16 12/20 kV: one core, copper 95 mm²; rated voltage 12/20 kV

Related cable types: YXC7V-R · YXC4V-R · YAXC8V-R · YXC2V-R · YXC3V-R

TS 621 / TSE (Turkey)

SymbolMeaning
YUnderground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212)
XCross-Linked Polyethylene (XLPE) Insulation
C8Copper Wire Screen Over Each Core
VPolyvinyl Chloride (PVC)
-RRound Stranded Conductor (Class 2)

How to read a TS 621 / TSE (Turkey) cable code

HAR: HD 361 harmonised designation (CENELEC)

SymbolMeaning
YTurkish TS Type For Medium And Heavy Operating Conditions (e.g. YXC7V-R)
XCross-Linked Polyethylene (XLPE)
C8Copper Screen, Over Individual Core
VPolyvinyl Chloride (PVC)
-RMulti-Wire, Round-Section, Class 2

How to read a HAR: HD 361 harmonised designation (CENELEC) cable code

How to read a TS 621 / TSE (Turkey) cable code

A TS 621 / TSE (Turkey) designation (Turkey) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 41 symbols for this system.

What does y mean in a TS 621 / TSE (Turkey) cable code? y means Flat Conductor; or Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212).

What does X mean in a TS 621 / TSE (Turkey) cable code? X means Cross-Linked Polyethylene (XLPE) Insulation.

What does C8 mean in a TS 621 / TSE (Turkey) cable code? C8 means Copper Wire Screen Over Each Core.

What does v mean in a TS 621 / TSE (Turkey) cable code? v means Flame Retardant; or Polyvinyl Chloride (PVC).

What does -R mean in a TS 621 / TSE (Turkey) cable code? -R means Round Stranded Conductor (Class 2).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

YXC8V-R: equivalents in other countries

Shown for 1x95/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
HD 620 S3 10-Lno letters for this buildEquivalentevery value the same
DenmarkHD 620 S3 10-Dno letters for this buildClosescreen 16 → 25 mm² (HD 620 10-D Table 1); this cable as built misses 1 of its rules
NorwayHD 620 S3 10-KTXSP 24 kV 1 x 95 mm2 (provisional code designation of HD 620 10-K Table 4; X is not explained in the standard)Closescreen 16 → 25 mm² (HD 620 10-K Table 1); Overall diameter 30.7 → 29.9 mm; this cable as built misses 1 of its rules
GermanyHD 620 S3 10-C (DIN VDE 0276-620)N2XSY 1x95 RM/16 12/20 kVCloseInsulation screen (semicon) 0.8 → 0.6 mm; Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.5 mm; this cable as built misses 3 of its rules
NetherlandsHD 620 S3 10-JYMvKrvas 12/20 kV 1x95 rs +as25 (key read from a maker (Nedkab), the NEN text not seen)Closescreen 16 → 25 mm² (HD 620 10-J Table A.1); Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.9 mm; this cable as built misses 1 of its rules
SwedenHD 620 S3 10-MFXCKJ 1x95/25 12/20 (24) kV (NKT writes a near build without the C (AXLJ))Closescreen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 30.7 → 29.5 mm; this cable as built misses 2 of its rules
EuropeHD 620 S3 10-Nno letters for this buildCloseInsulation 5.5 → 4.8 mm; Sheath material PVC → PE; Sheath 1.9 → 1.8 mm; Overall diameter 30.7 → 29.1 mm
EuropeHD 620 S3 10-Pno letters for this buildCloseWire screen material: not in the equivalent; Sheath 1.9 → 2.7 mm; Tape screen material: only in the equivalent; Overall diameter 30.7 → 30.9 mm; this cable as built misses 1 of its rules
United KingdomHD 620 S3 10-Ono letters for this buildCloserated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen wire diameter 0.7 → 1.04 mm; this cable as built misses 1 of its rules
IndiaIS 7098 (Part 2)2XY 1x95 12.7/22 kVCloserated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 2.2 mm; this cable as built misses 2 of its rules
HD 620 S3 10-Gno letters for this buildCloseInsulation 5.5 → 4.4 mm; Wire screen material: not in the equivalent; Sheath material PVC → PE; Sheath 1.9 → 1.8 mm

No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-E1 (the size, cores or voltage would change); HD 620 S3 10-E2 (the size, cores or voltage would change); HD 620 S3 10-I1 (the size, cores or voltage would change); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

YXC8V-R as the cable designer builds it, 1x95/16 12/20 kV

Overall diameter 30.7 mm, about 1,640 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
Conductor screen (semicon)Semiconducting0.6012.7
InsulationXLPE5.523.7
Insulation screen (semicon)Semiconducting0.8025.3
Wire screenCopper42 × 0.7026.9
SheathPVC1.930.7

YXC8V-R on a drum

The smallest drum that passes every check, for 30.7 mm and about 1,640 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG7 of 121,096–1,129 kg
1,000 mKTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG12 of 121,916–1,949 kg

Barrel at least 25 × OD = 768 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: YXC8V-R

YXC8V-R belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Accessories for this cable

Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).

  • Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
  • Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
  • Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
  • Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
  • Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
  • Cold shrink straight joints, Um 24 kV: conductor 95–300 mm²

Typical; no maker or kit is named, and your kit's own sheet decides.

Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro

Work with YXC8V-R

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More TS 621 / TSE (Turkey) designations

YXC8V-R