YAXC8V-R
YAXC8V-R is a TS 621 / TSE (Turkey) cable designation: Y = Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212); A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE) Insulation; C8 = Copper Wire Screen Over Each Core; V = Polyvinyl Chloride (PVC); -R = Round Stranded Conductor (Class 2).
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of YAXC8V-R 1x95/16 12/20 kV:
YAXC8V-R: Y = Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212); A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE) Insulation; C8 = Copper Wire Screen Over Each Core; V = Polyvinyl Chloride (PVC); -R = Round Stranded Conductor (Class 2)1x95/16 12/20 kV: one core, aluminium 95 mm²; rated voltage 12/20 kV
Related cable types: YAXC7V-R · YXC8V-R · YXC7V-R · YAXV-R · YXC4V-R · YXC2V-R
TS 621 / TSE (Turkey)
| Symbol | Meaning |
|---|---|
Y | Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212) |
A | Aluminium Conductor |
X | Cross-Linked Polyethylene (XLPE) Insulation |
C8 | Copper Wire Screen Over Each Core |
V | Polyvinyl Chloride (PVC) |
-R | Round Stranded Conductor (Class 2) |
HAR: HD 361 harmonised designation (CENELEC)
| Symbol | Meaning |
|---|---|
Y | Turkish TS Type For Medium And Heavy Operating Conditions (e.g. YXC7V-R) |
A | Concentric Aluminium Conductor |
X | Cross-Linked Polyethylene (XLPE) |
C8 | Copper Screen, Over Individual Core |
V | Polyvinyl Chloride (PVC) |
-R | Multi-Wire, Round-Section, Class 2 |
How to read a HAR: HD 361 harmonised designation (CENELEC) cable code
How to read a TS 621 / TSE (Turkey) cable code
A TS 621 / TSE (Turkey) designation (Turkey) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 41 symbols for this system.
What does y mean in a TS 621 / TSE (Turkey) cable code? y means Flat Conductor; or Underground Heavy-Duty Cable For Fixed Installation (Y Cable Family, TS 212).
What does A mean in a TS 621 / TSE (Turkey) cable code? A means Aluminium Conductor.
What does X mean in a TS 621 / TSE (Turkey) cable code? X means Cross-Linked Polyethylene (XLPE) Insulation.
What does C8 mean in a TS 621 / TSE (Turkey) cable code? C8 means Copper Wire Screen Over Each Core.
What does v mean in a TS 621 / TSE (Turkey) cable code? v means Flame Retardant; or Polyvinyl Chloride (PVC).
What does -R mean in a TS 621 / TSE (Turkey) cable code? -R means Round Stranded Conductor (Class 2).
Fire behaviour (EU CPR)
PVC sheath (V).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
YAXC8V-R: equivalents in other countries
Shown for 1x95/16 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| HD 620 S3 10-L | no letters for this build | Equivalent | every value the same | |
| Denmark | HD 620 S3 10-D | no letters for this build | Close | screen 16 → 25 mm² (HD 620 10-D Table 1); this cable as built misses 1 of its rules |
| Norway | HD 620 S3 10-K | TXSP 24 kV 1 x 95 mm2 A (provisional code designation of HD 620 10-K Table 4; X is not explained in the standard) | Close | screen 16 → 25 mm² (HD 620 10-K Table 1); Overall diameter 30.7 → 29.9 mm; this cable as built misses 1 of its rules |
| Germany | HD 620 S3 10-C (DIN VDE 0276-620) | NA2XSY 1x95 RM/16 12/20 kV | Close | Insulation screen (semicon) 0.8 → 0.6 mm; Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.5 mm; this cable as built misses 3 of its rules |
| Sweden | HD 620 S3 10-M | AXCKJ 1x95/25 12/20 (24) kV (NKT writes a near build without the C (AXLJ)) | Close | screen 16 → 25 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 30.7 → 29.5 mm; this cable as built misses 2 of its rules |
| Netherlands | HD 620 S3 10-J | YMvKrvas 12/20 kV 1x95 Al rs +as25 (key read from a maker (Nedkab), the NEN text not seen) | Close | screen 16 → 25 mm² (HD 620 10-J Table A.1); Sheath 1.9 → 2.5 mm; Overall diameter 30.7 → 31.9 mm; this cable as built misses 2 of its rules |
| Europe | HD 620 S3 10-N | no letters for this build | Close | Insulation 5.5 → 4.8 mm; Sheath material PVC → PE; Sheath 1.9 → 1.8 mm; Overall diameter 30.7 → 29.1 mm |
| Europe | HD 620 S3 10-P | no letters for this build | Close | Wire screen material: not in the equivalent; Sheath 1.9 → 2.7 mm; Tape screen material: only in the equivalent; Overall diameter 30.7 → 30.9 mm; this cable as built misses 1 of its rules |
| United Kingdom | HD 620 S3 10-O | no letters for this build | Close | rated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen wire diameter 0.7 → 1.04 mm; this cable as built misses 1 of its rules |
| Spain | HD 620 S3 10-E1 | RHZ1-OL 12/20 kV 1 x 95 K Al + H16 | Close | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Sheath material PVC → LSZH; Sheath 1.9 → 2.7 mm; this cable as built misses 1 of its rules |
| India | IS 7098 (Part 2) | A2XY 1x95 12.7/22 kV | Close | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Wire screen material: not in the equivalent; Sheath 1.9 → 2.2 mm; this cable as built misses 2 of its rules |
| Spain | HD 620 S3 10-E2 | no letters for this build | Close | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation 5.5 → 4.9 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I1 | ARE4H5EX 12/20 kV 1 x 95 | Close | Insulation 5.5 → 4.31 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Sheath material PVC → PE; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I2 | ARE4H5EX 12/20 kV 1 x 95 | Close | Insulation 5.5 → 4.3 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Sheath material PVC → PE; this cable as built misses 1 of its rules |
| HD 620 S3 10-G | no letters for this build | Close | Insulation 5.5 → 4.4 mm; Wire screen material: not in the equivalent; Sheath material PVC → PE; Sheath 1.9 → 1.8 mm |
No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-I3 (the size, cores or voltage would change).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
YAXC8V-R as the cable designer builds it, 1x95/16 12/20 kV
Overall diameter 30.7 mm, about 1,040 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.60 | 12.7 |
| Insulation | XLPE | 5.5 | 23.7 |
| Insulation screen (semicon) | Semiconducting | 0.80 | 25.3 |
| Wire screen | Copper | 42 × 0.70 | 26.9 |
| Sheath | PVC | 1.9 | 30.7 |
YAXC8V-R on a drum
The smallest drum that passes every check, for 30.7 mm and about 1,040 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 12 | 796–829 kg |
| 1,000 m | KTG 16 (1600 mm flange), wood KTG drums (Europe), Bayka, KTG | 12 of 12 | 1,316–1,349 kg |
Barrel at least 25 × OD = 768 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: YAXC8V-R
YAXC8V-R belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Accessories for this cable
Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).
- Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
- Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
- Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
- Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
- Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
- Cold shrink straight joints, Um 24 kV: conductor 95–300 mm²
Typical; no maker or kit is named, and your kit's own sheet decides.
Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro