NYIF
NYIF is a DIN VDE type names (Germany) cable designation: N = German national (VDE) type; Y = PVC core insulation (YI 1); IF = Stegleitung: flat webbed wire, the cores side by side in a common outer covering joined by a web; without a further letter the covering is rubber (NYIF); Y = Outer covering of PVC (YM 1), NYIFY; NYIF = NYIF / NYIFY: flat webbed installation wire (Stegleitung), PVC insulated solid copper cores side by side in an outer covering of rubber (NYIF) or PVC (NYIFY). U0/U 230/400 V (clause 3); for laying in and under plaster, DIN VDE 0298-3 (clause 6). DIN VDE 0250-201:1992-09 (2 and 3 cores 1,5 to 4 mm², 4 and 5 cores 1,5 and 2,5 mm², 4.1; bare solid copper class 1, 4.2; PVC insulation YI 1, 0,4 / 0,5 / 0,6 mm at 1,5 / 2,5 / 4 mm², 4.3 and Table 1 column 6; cores side by side, 4.5; outer covering vulcanised rubber (NYIF) or PVC YM 1 (NYIFY), 0,8 / 0,9 / 0,9 mm, Table 1 column 7, with a wedge-shaped groove at least 0,3 mm deep in the middle of the web on both sides, 4.6; core colours DIN VDE 0293, 4.4).
1 coding system recognises this code
DIN VDE type names (Germany)
| Symbol | Meaning |
|---|---|
N | German national (VDE) type |
Y | PVC core insulation (YI 1) |
IF | Stegleitung: flat webbed wire, the cores side by side in a common outer covering joined by a web; without a further letter the covering is rubber (NYIF) |
Y | Outer covering of PVC (YM 1), NYIFY |
NYIF | NYIF / NYIFY: flat webbed installation wire (Stegleitung), PVC insulated solid copper cores side by side in an outer covering of rubber (NYIF) or PVC (NYIFY). U0/U 230/400 V (clause 3); for laying in and under plaster, DIN VDE 0298-3 (clause 6). DIN VDE 0250-201:1992-09 (2 and 3 cores 1,5 to 4 mm², 4 and 5 cores 1,5 and 2,5 mm², 4.1; bare solid copper class 1, 4.2; PVC insulation YI 1, 0,4 / 0,5 / 0,6 mm at 1,5 / 2,5 / 4 mm², 4.3 and Table 1 column 6; cores side by side, 4.5; outer covering vulcanised rubber (NYIF) or PVC YM 1 (NYIFY), 0,8 / 0,9 / 0,9 mm, Table 1 column 7, with a wedge-shaped groove at least 0,3 mm deep in the middle of the web on both sides, 4.6; core colours DIN VDE 0293, 4.4) |
What is NYIF cable?
NYIF: NYIF / NYIFY: flat webbed installation wire (Stegleitung), PVC insulated solid copper cores side by side in an outer covering of rubber (NYIF) or PVC (NYIFY). Rating: U0/U 230/400 V (clause 3); for laying in and under plaster, DIN VDE 0298-3 (clause 6). Standard: DIN VDE 0250-201:1992-09 (2 and 3 cores 1,5 to 4 mm², 4 and 5 cores 1,5 and 2,5 mm², 4.1; bare solid copper class 1, 4.2; PVC insulation YI 1, 0,4 / 0,5 / 0,6 mm at 1,5 / 2,5 / 4 mm², 4.3 and Table 1 column 6; cores side by side, 4.5; outer covering vulcanised rubber (NYIF) or PVC YM 1 (NYIFY), 0,8 / 0,9 / 0,9 mm, Table 1 column 7, with a wedge-shaped groove at least 0,3 mm deep in the middle of the web on both sides, 4.6; core colours DIN VDE 0293, 4.4).
Table 1 (minimum width / maximum outer dimensions, mm): 2x1,5 10,5 / 4,4 x 12; 2x2,5 12 / 5,2 x 13,5; 2x4 14 / 6 x 15,5; 3x1,5 17,5 / 4,4 x 19; 3x2,5 19,5 / 5,2 x 21,5; 3x4 23 / 6 x 25; 4x1,5 24 / 4,4 x 26; 4x2,5 27 / 5,2 x 29,5; 5x1,5 31 / 4,4 x 33; 5x2,5 34,5 / 5,2 x 37. Two cores are -O only; three to five -O or -J. The 0,4 mm insulation may be at no point below 0,30 mm (4.3). NYIF's rubber covering need not be a DIN VDE 0207-21 compound (4.6 a). The decoder draws the cores round, not webbed.
Documents and pages the readings were taken from
- DIN VDE 0250-201:1992-09 (clauses 2 to 6 p. 2, Table 1 pp. 3 to 4)
DIN VDE type names (Germany): how to read the cable type names
Fire behaviour (EU CPR)
PVC sheath (Y).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
Laying, sizes and datasheet: NYIF
Terms on this page: wedge (chock)