MOBILE HOME FEEDER is a NEC / UL (USA) cable designation: MOBILE HOME FEEDER = Mobile home feeder: three aluminium alloy conductors and an insulated ground, XLPE insulated (USE-2 / RHH / RHW-2), direct burial. 600 V, 90 C wet or dry. UL 44; UL 854 (USE-2).
1 coding system recognises this code
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
MOBILE HOME FEEDER | Mobile home feeder: three aluminium alloy conductors and an insulated ground, XLPE insulated (USE-2 / RHH / RHW-2), direct burial. 600 V, 90 C wet or dry. UL 44; UL 854 (USE-2) |
What is MOBILE HOME FEEDER cable?
MOBILE HOME FEEDER: Mobile home feeder: three aluminium alloy conductors and an insulated ground, XLPE insulated (USE-2 / RHH / RHW-2), direct burial. Rating: 600 V, 90 C wet or dry. Standard: UL 44; UL 854 (USE-2).
Two makers agree (Southwire SPEC 10054, Prysmian / General Cable SPEC 5940A p. 1, June 2017, read 2026-11-03): "2-2-2-4" is two phase conductors and a neutral of 2 AWG and a 4 AWG ground, class B compact stranded 8000 series aluminium alloy (AA-8176 at Southwire, AA-8030 at Prysmian), XLPE 60 mil on every conductor, UL type USE-2 / RHH / RHW-2, 600 V, 90 C wet or dry, UL 44 and UL 854, no overall jacket. Colours are not shown: the neutral is black with a white stripe (Southwire).
Documents and pages the readings were taken from
Laying, sizes and datasheet: MOBILE HOME FEEDER
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Terms on this page: direct burial
Work with MOBILE HOME FEEDER
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.