MC

MC is a NEC / UL (USA) cable designation: MC = Metal-clad cable; MC = Metal-clad cable: insulated conductors and a green ground in interlocked metal armour. 600 V, 90 C conductors. UL 1569; NEC Article 330.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: UL 1569: Metal-Clad Cables. How the values are sourced

Worked reading of MC 3/C 12 AWG, 600 V:

  • MC: MC = Metal-clad cable; MC = Metal-clad cable: insulated conductors and a green ground in interlocked metal armour. 600 V, 90 C conductors. UL 1569; NEC Article 330
  • 3/C 12 AWG, 600 V: 3 cores, each copper 12 AWG (3.3 mm²); rated voltage 600 V

Related cable types: MCs · MCEC · MC-HL · MCMK · MMCu · AMCMK

NEC / UL (USA)

SymbolMeaning
MCMetal-clad cable
MCMetal-clad cable: insulated conductors and a green ground in interlocked metal armour. 600 V, 90 C conductors. UL 1569; NEC Article 330

Norwegian type designation (NEK 606 offshore and Norwegian land cables)

SymbolMeaning
MExpanded PE Or PP + Filling Compound
CPolychloroprene (Neoprene, PCP) or Chlorinated Polyethylene (CPE) (Nexans Norway key: improved hydrocarbon resistance)

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

What is MC cable?

MC: Metal-clad cable: insulated conductors and a green ground in interlocked metal armour. Rating: 600 V, 90 C conductors. Standard: UL 1569; NEC Article 330.

12/2 MC is two conductors plus a green insulated ground. Southwire ArmorLite uses XHHW-2 XLPE (no nylon) with Mylar tape and adds a bare copper ground; MC Lite THHN/THWN-2 versions use PVC with nylon. Armour is aluminium or galvanised steel. Also typed with the insulation: "MC THHN", "MC XHHW".

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

MC as the cable designer builds it, 3/C 12 AWG, 600 V

Overall diameter 13.1 mm, about 200 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.382.8
Nylon jacket (polyamide)Nylon (PA)0.103.0
Ground conductor: InsulationPVC0.382.8
Ground conductor: Nylon jacket (polyamide)Nylon (PA)0.103.0
Separation tapePolyester0.107.5
Interlocked armourAluminium2.813.1

MC on a drum

The smallest drum that passes every check, for 13.1 mm and about 200 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 30x18x12, wood NEMA reels (North America), American Wire Group, Okonite12 of 14118–120 kg
1,000 mNEMA 32x24x14, wood NEMA reels (North America), American Wire Group, Okonite14 of 14225–230 kg

Barrel at least 15 × OD = 196 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: MC

MC belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with MC

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations