CE

CE is a JIS type names (Japan) cable designation: C = C: cross-linked polyethylene (XLPE) insulation; E = E: polyethylene sheath; CE = CE: XLPE insulated, polyethylene sheathed power cable (CE/F: flame-retardant polyethylene sheath). 600 V (SF-0027); 0.6/1 kV and 6/10 kV (Taihan). JIS C 3605 (600 V); JCS 4516 (3300 V); JIS C 3606 (6600 V); KS C IEC 60502-1 / -2 (Korea).

6 coding systems recognise this code

JIS type names (Japan)

SymbolMeaning
CC: cross-linked polyethylene (XLPE) insulation
EE: polyethylene sheath
CECE: XLPE insulated, polyethylene sheathed power cable (CE/F: flame-retardant polyethylene sheath). 600 V (SF-0027); 0.6/1 kV and 6/10 kV (Taihan). JIS C 3605 (600 V); JCS 4516 (3300 V); JIS C 3606 (6600 V); KS C IEC 60502-1 / -2 (Korea)

China (GB / JB/T / MT cable model codes)

SymbolMeaning
CShipboard or Marine Cable
ELow Smoke Zero Halogen Compound

How to read a China (GB / JB/T / MT cable model codes) cable code

Norwegian type designation (NEK 606 offshore and Norwegian land cables)

SymbolMeaning
CPolychloroprene (Neoprene - PCP), Or Chlorinated Polyethylene (CPE)
EPolyethylene (PE) or Polypropylene (PP)

How to read a Norwegian type designation (NEK 606 offshore and Norwegian land cables) cable code

NBN (Belgian national cable names, ...B types)

SymbolMeaning
CRubber (Caoutchouc), Natural Or Synthetic, Insulation Or Sheath
EUltra Fine-Wired, For Welding Cables

How to read a NBN (Belgian national cable names, ...B types) cable code

IEEE 1580

SymbolMeaning
CConductor Control Cable
EEthylene-Propylene Rubber (EPR)

How to read a IEEE 1580 cable code

NEN 3207 / KEMA (Netherlands)

SymbolMeaning
CChloroprene Rubber
EPolyethylene (PE)

How to read a NEN 3207 / KEMA (Netherlands) cable code

Fire behaviour (EU CPR)

  • Flame retardant (CE). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.

  • PE sheath (E, CE).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

Work with CE

Related cables

More JIS type names (Japan) designations