CCES
CCES is a KS / KEPCO type names (Korea) cable designation: C = C: control cable (first letter of the control cable names CVV, CCV, CCE, HFCCO); C = C: cross-linked polyethylene (XLPE) insulation; E = E: polyethylene sheath; S = S: copper tape shield over the laid-up cores; CCES = CCES: 0.6/1 kV XLPE insulated control cable with a copper tape shield and a polyethylene sheath. 0.6/1 kV (Taihan p.33). KS C IEC 60502-1.
3 coding systems recognise this code
KS / KEPCO type names (Korea)
| Symbol | Meaning |
|---|---|
C | C: control cable (first letter of the control cable names CVV, CCV, CCE, HFCCO) |
C | C: cross-linked polyethylene (XLPE) insulation |
E | E: polyethylene sheath |
S | S: copper tape shield over the laid-up cores |
CCES | CCES: 0.6/1 kV XLPE insulated control cable with a copper tape shield and a polyethylene sheath. 0.6/1 kV (Taihan p.33). KS C IEC 60502-1 |
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
C | Shipboard or Marine Cable |
C | Heavy Duty (Characteristic Letter, As In YC) |
E | Low Smoke Zero Halogen Compound |
S | Stranded Conductor |
How to read a China (GB / JB/T / MT cable model codes) cable code
NEN 3207 / KEMA (Netherlands)
| Symbol | Meaning |
|---|---|
C | Chloroprene Rubber |
C | Chloroprene Rubber |
E | Polyethylene (PE) |
S | Silicone Rubber |
Fire behaviour (EU CPR)
PE sheath (E).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
CCES as the cable designer builds it, 4x1.5 0.6/1 kV
Overall diameter 12.7 mm, about 200 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | XLPE | 0.70 | 2.8 |
| Filler | PP | 6.7 | |
| Inner covering / bedding | PVC | 1.0 | 8.7 |
| Tape screen | Copper | 0.20 | 9.1 |
| Sheath | PE | 1.8 | 12.7 |
CCES on a drum
The smallest drum that passes every check, for 12.7 mm and about 200 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG | 11 of 11 | 131–135 kg |
| 1,000 m | KTG 9 (900 mm flange), wood KTG drums (Europe), Bayka, KTG | 13 of 13 | 247–251 kg |
Barrel at least 15 × OD = 191 mm for a cable of this kind (Low voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: CCES
CCES belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables