AXCEL

AXCEL is a China (GB / JB/T / MT cable model codes) cable designation: A = Twin Cable; X = Natural Or Styrene-Butadiene Rubber; C = Heavy Duty (Characteristic Letter, As In YC); E = Low Smoke Zero Halogen Compound; L = Aluminium Conductor.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of AXCEL 1x16 0.6/1 kV:

  • AXCEL: A = Twin Cable; X = Natural Or Styrene-Butadiene Rubber; C = Heavy Duty (Characteristic Letter, As In YC); E = Low Smoke Zero Halogen Compound; L = Aluminium Conductor
  • 1x16 0.6/1 kV: one core, aluminium 16 mm²; rated voltage 0.6/1 kV

China (GB / JB/T / MT cable model codes)

SymbolMeaning
ATwin Cable
XNatural Or Styrene-Butadiene Rubber
CHeavy Duty (Characteristic Letter, As In YC)
ELow Smoke Zero Halogen Compound
LAluminium Conductor

How to read a China (GB / JB/T / MT cable model codes) cable code

CEI-UNEL 35011 (Italy)

SymbolMeaning
AAluminium Conductor
XHelically Bundled Visible Cores
CConcentric Copper Conductor
ELLead Alloy Sheath, With Continuity Conductor Below

How to read a CEI-UNEL 35011 (Italy) cable code

How to read a China (GB / JB/T / MT cable model codes) cable code

A China (GB / JB/T / MT cable model codes) designation (China) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 137 symbols for this system.

What does A mean in a China (GB / JB/T / MT cable model codes) cable code? A means Twin Cable; or Aluminium Foil With Polyethylene Sheath.

What does X mean in a China (GB / JB/T / MT cable model codes) cable code? X means Natural Or Styrene-Butadiene Rubber.

What does C mean in a China (GB / JB/T / MT cable model codes) cable code? C means Shipboard or Marine Cable; or Heavy Duty (Characteristic Letter, As In YC).

What does E mean in a China (GB / JB/T / MT cable model codes) cable code? E means Low Smoke Zero Halogen Compound.

What does L mean in a China (GB / JB/T / MT cable model codes) cable code? L means Aluminium Conductor; or Aluminium Sheath.

Fire behaviour (EU CPR)

  • Halogen-free compound (E). Under the CPR this shows in the additional classes: acidity a1 to a3 (EN 60754-2) and smoke s1 to s3 (EN 50399; s1a and s1b add the 3 m cube test EN 61034-2). The main class, Aca to Fca, depends on the whole construction.

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

AXCEL as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.7 mm, about 120 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationEPR1.06.9
SheathHalogen-free (LSZH)1.49.7

AXCEL on a drum

The smallest drum that passes every check, for 9.7 mm and about 120 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 1467 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 16151–155 kg

Barrel at least 20 × OD = 194 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: AXCEL

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 7.4 %. Sources: IEC 60364-5-52:2009, Table B.52.5, p. 44; IEC 60228:2023 Table 4, p. 13; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits