AXLJ-TTCL TSLF
AXLJ-TTCL TSLF is a Norsk typebetegnelse (Norway) cable designation: T = 1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen'); S = 2nd letter: bedding or taping plus concentric conductor ('Fyllkappe/baandering + konsentrisk leder'), used when the 3rd letter is taken; L = 3rd letter: aluminium laminate ('Aluminiumlaminat'); F = 4th letter, outer sheath: semiconducting PE ('Halvledende PE'); TSLF = TSLF: single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen, aluminium laminate bonded to a PE sheath with an outer semiconducting layer (three cores laid up as 3x1x...). 12/20 (24) kV and 18/30 (36) kV on the pages read (also 12 kV and up to 145 kV in the handbook). Norwegian type designation as tabled in the Nexans Kabelboka (part 2, 'Norske typebetegnelser for kabler'); construction HD 620.10K.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of AXLJ-TTCL TSLF 1x240/25 12/20 kV:
AXLJ-TTCL TSLF: T = 1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen'); S = 2nd letter: bedding or taping plus concentric conductor ('Fyllkappe/baandering + konsentrisk leder'), used when the 3rd letter is taken; L = 3rd letter: aluminium laminate ('Aluminiumlaminat'); F = 4th letter, outer sheath: semiconducting PE ('Halvledende PE'); TSLF = TSLF: single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen, aluminium laminate bonded to a PE sheath with an outer semiconducting layer (three cores laid up as 3x1x...). 12/20 (24) kV and 18/30 (36) kV on the pages read (also 12 kV and up to 145 kV in the handbook). Norwegian type designation as tabled in the Nexans Kabelboka (part 2, 'Norske typebetegnelser for kabler'); construction HD 620.10K1x240/25 12/20 kV: one core, aluminium 240 mm²; rated voltage 12/20 kV
Related cable types: TSLF
Norsk typebetegnelse (Norway)
| Symbol | Meaning |
|---|---|
T | 1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen') |
S | 2nd letter: bedding or taping plus concentric conductor ('Fyllkappe/baandering + konsentrisk leder'), used when the 3rd letter is taken |
L | 3rd letter: aluminium laminate ('Aluminiumlaminat') |
F | 4th letter, outer sheath: semiconducting PE ('Halvledende PE') |
TSLF | TSLF: single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen, aluminium laminate bonded to a PE sheath with an outer semiconducting layer (three cores laid up as 3x1x...). 12/20 (24) kV and 18/30 (36) kV on the pages read (also 12 kV and up to 145 kV in the handbook). Norwegian type designation as tabled in the Nexans Kabelboka (part 2, 'Norske typebetegnelser for kabler'); construction HD 620.10K |
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
A | Twin Cable |
X | Natural Or Styrene-Butadiene Rubber |
L | Aluminium Conductor |
J | Stranded Conductor |
T | Copper Conductor |
T | Copper Conductor |
C | Heavy Duty (Characteristic Letter, As In YC) |
L | Aluminium Conductor |
T | Copper Conductor |
S | Silicone Rubber |
L | Aluminium Conductor |
F | Chloroprene Rubber |
How to read a China (GB / JB/T / MT cable model codes) cable code
What is TSLF cable?
TSLF: single-core medium-voltage cable, aluminium conductor, XLPE insulation, copper wire screen, aluminium laminate bonded to a PE sheath with an outer semiconducting layer (three cores laid up as 3x1x...). Rating: 12/20 (24) kV and 18/30 (36) kV on the pages read (also 12 kV and up to 145 kV in the handbook). Standard: Norwegian type designation as tabled in the Nexans Kabelboka (part 2, 'Norske typebetegnelser for kabler'); construction HD 620.10K.
Nexans: 'Metal screened cable with laminated aluminium sheet and outer semiconducting layer. Tree twisted cores.' 3x1x95A is three single cores laid up, each screened and sheathed; the A after the section is aluminium (the handbook writes 1x95A, letter not defined there). The handbook's 2nd column S is only used when the 3rd letter is taken, as here by L.
Documents and pages the readings were taken from
Norsk typebetegnelse (Norway): how to read the cable type names
Fire behaviour (EU CPR)
PE sheath (F).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
AXLJ-TTCL TSLF: equivalents in other countries
Shown for 1x240/25 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | Al/XLPE/CWS/PE 1x240/25 12/20 kV (to IEC 60502-2) | Equivalent | Sheath 2.2 → 2.1 mm; Overall diameter 39 → 39.6 mm |
| Netherlands | HD 620 S3 10-J | YMeKrvasdlwd 12/20 kV 1x240 Al rs +as25 (key read from a maker (Nedkab), the NEN text not seen) | Close | Sheath 2.2 → 2.5 mm; Overall diameter 39 → 40.4 mm; this cable as built misses 1 of its rules |
| Germany | HD 620 S3 10-C (DIN VDE 0276-620) | NA2XS(FL)2Y 1x240 RM/25 12/20 kV | Close | Insulation screen (semicon) 0.8 → 0.6 mm; Sheath 2.2 → 2.5 mm; Overall diameter 39 → 40 mm; this cable as built misses 2 of its rules |
| Denmark | HD 620 S3 10-D | PEX-AL 1x240+35 12/20 (24) kV (the letters do not say the laminate and the water block) | Close | screen 25 → 35 mm² (HD 620 10-D Table 1); Overall diameter 39 → 39.8 mm; this cable as built misses 1 of its rules |
| Sweden | HD 620 S3 10-M | AXCLJ-TT 1x240/35 12/20 (24) kV (NKT writes a near build without the C (AXLJ)) | Close | screen 25 → 35 mm² (HD 620 10-M Tables 1A, 2A, 3A); Insulation screen (semicon) 0.8 → 0.6 mm; Overall diameter 39 → 38.6 mm; this cable as built misses 2 of its rules |
| HD 620 S3 10-L | no letters for this build | Close | Swelling tape (water block) material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Laminate (radial water block) material: not in the equivalent; Sheath material PE → PVC | |
| Spain | HD 620 S3 10-E1 | RHZ1-OL 12/20 kV 1 x 240 K Al + H16 | Close | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen section 25 → 16 mm²; Swelling tape (water block) material: not in the equivalent; this cable as built misses 1 of its rules |
| Europe | HD 620 S3 10-N | no letters for this build | Close | Insulation 5.5 → 4.8 mm; Swelling tape (water block) material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Laminate (radial water block) material: not in the equivalent |
| United Kingdom | HD 620 S3 10-O | no letters for this build | Close | rated 12.7/22 kV (same Um 24 kV); Conductor screen (semicon) 0.6 → 0.7 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Swelling tape (water block) material: not in the equivalent; this cable as built misses 1 of its rules |
| HD 620 S3 10-G | no letters for this build | Close | Insulation 5.5 → 4.3 mm; Wire screen material: not in the equivalent; Laminate (radial water block) material: not in the equivalent; Sheath 2.2 → 2 mm | |
| Spain | HD 620 S3 10-E2 | no letters for this build | Close | Conductor screen (semicon) 0.6 → 0.5 mm; Insulation 5.5 → 4.9 mm; Insulation screen (semicon) 0.8 → 0.5 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules |
| Italy | HD 620 S3 10-I1 | ARE4H5EX 12/20 kV 1 x 240 | Close | Insulation 5.5 → 4.31 mm; Insulation screen (semicon) 0.8 → 0.6 mm; Wire screen material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; this cable as built misses 2 of its rules |
| Europe | HD 620 S3 10-P | no letters for this build | Close | Swelling tape (water block) material: not in the equivalent; Wire screen material: not in the equivalent; Swelling tape (water block) material: not in the equivalent; Laminate (radial water block) material: not in the equivalent; this cable as built misses 1 of its rules |
| India | IS 7098 (Part 2) | A2X2Y 1x240 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3) | Close | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Swelling tape (water block) material: not in the equivalent; Wire screen material: not in the equivalent; this cable as built misses 1 of its rules |
No equivalent in: BS 6622 (armoured cables only); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
AXLJ-TTCL TSLF as the cable designer builds it, 1x240/25 12/20 kV
Overall diameter 39.0 mm, about 1,710 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.60 | 19.6 |
| Insulation | XLPE | 5.1 | 29.8 |
| Insulation screen (semicon) | Semiconducting | 0.80 | 31.4 |
| Swelling tape (water block) | Swelling | 0.30 | 32.0 |
| Wire screen | Copper | 65 × 0.70 | 33.6 |
| Swelling tape (water block) | Swelling | 0.30 | 34.2 |
| Laminate (radial water block) | Aluminium | 0.20 | 34.6 |
| Sheath | PE | 2.2 | 39.0 |
AXLJ-TTCL TSLF on a drum
The smallest drum that passes every check, for 39 mm and about 1,710 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 18 (1800 mm flange), wood KTG drums (Europe), Bayka, KTG | 7 of 9 | 1,196–1,268 kg |
| 1,000 m | KTG 20 (2000 mm flange), wood KTG drums (Europe), Bayka, KTG | 9 of 9 | 2,189–2,310 kg |
Barrel at least 25 × OD = 975 mm for a cable of this kind (Medium voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: AXLJ-TTCL TSLF
AXLJ-TTCL TSLF belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables
Terms on this page: bedding · oversheath (outer sheath)
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Accessories for this cable
Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).
- Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
- Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
- Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
- Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
- Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
- Cold shrink straight joints, Um 24 kV: conductor 95–300 mm²
Typical; no maker or kit is named, and your kit's own sheet decides.
Pro: the range that fits your own cable, the length the kit takes along the cable end and its shed count, fitted in 3D. Cable end preparation in the cable designer · See Pro
Work with AXLJ-TTCL TSLF
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.