AXCLJ-TT
AXCLJ-TT is a SS 424 17 01 (Sweden) cable designation: A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE, PEX); C = Concentric Copper-Wire Screen (Concentric Conductor); L = Polyethylene (PE); J = For Laying In Ground; TT = Transversely And Longitudinally Water-Tight Construction.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60502-2:2014 (edition 3.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 2: Cables for rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV); HD 620 S3:2023: Distribution cables with extruded insulation for rated voltages from 3,6/6 (7,2) kV up to and including 20,8/36 (42) kV; IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of AXCLJ-TT 3x95/25 12/20 kV:
AXCLJ-TT: A = Aluminium Conductor; X = Cross-Linked Polyethylene (XLPE, PEX); C = Concentric Copper-Wire Screen (Concentric Conductor); L = Polyethylene (PE); J = For Laying In Ground; TT = Transversely And Longitudinally Water-Tight Construction3x95/25 12/20 kV: 3 cores, each aluminium 95 mm²; rated voltage 12/20 kV
SS 424 17 01 (Sweden)
| Symbol | Meaning |
|---|---|
A | Aluminium Conductor |
X | Cross-Linked Polyethylene (XLPE, PEX) |
C | Concentric Copper-Wire Screen (Concentric Conductor) |
L | Polyethylene (PE) |
J | For Laying In Ground |
TT | Transversely And Longitudinally Water-Tight Construction |
China (GB / JB/T / MT cable model codes)
| Symbol | Meaning |
|---|---|
A | Twin Cable |
X | Natural Or Styrene-Butadiene Rubber |
C | Heavy Duty (Characteristic Letter, As In YC) |
L | Aluminium Conductor |
J | Cross-linked polyethylene XLPE |
T | Copper Conductor |
T | Copper Conductor |
How to read a China (GB / JB/T / MT cable model codes) cable code
How to read a SS 424 17 01 (Sweden) cable code
A SS 424 17 01 (Sweden) designation (Sweden) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 90 symbols for this system.
What does A mean in a SS 424 17 01 (Sweden) cable code? A means Aluminium Conductor; or Screen Of Aluminium Foil And/Or Aluminium Wire.
What does X mean in a SS 424 17 01 (Sweden) cable code? X means Cross-Linked Polyethylene (XLPE, PEX); or Polyvinyl Chloride (PVC), Oval Section; or Without Protective Conductor (Size Field).
What does C mean in a SS 424 17 01 (Sweden) cable code? C means Impregnated Paper Insulation; or Concentric Copper-Wire Screen (Concentric Conductor); or Concentric Copper Screen.
What does L mean in a SS 424 17 01 (Sweden) cable code? L means Polyethylene (PE); or Screen Of Plastic-Coated Aluminium Tape (Possibly With A Copper Screen); Or Polyethylene (PE) Sheath.
What does J mean in a SS 424 17 01 (Sweden) cable code? J means Steel Wire Conductor; or Steel Tape Armour; or Underground Use; or For Laying In Ground.
What does TT mean in a SS 424 17 01 (Sweden) cable code? TT means Transversely And Longitudinally Water-Tight Construction.
Fire behaviour (EU CPR)
PE sheath (L).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
FcaYMeKrvaslqwd, TKFFcaNA2XS(F)2Y, Waskönig+Walter
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
AXCLJ-TT: equivalents in other countries
Shown for 3x95/25 12/20 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| Norway | HD 620 S3 10-K | no letters for this build | Equivalent | Insulation screen (semicon) 0.6 → 0.8 mm; Overall diameter 59.53 → 60.39 mm |
| Denmark | HD 620 S3 10-D | PEX-AL 3x95+25 12/20 (24) kV (the letters do not say the laminate and the water block) | Equivalent | Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 3 → 2.9 mm; Overall diameter 59.53 → 61.91 mm |
| International (IEC) | IEC 60502 | Al/XLPE/CWS/PE 3x95/25 12/20 kV (to IEC 60502-2) | Equivalent | Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 3 → 2.9 mm; Overall diameter 59.53 → 61.91 mm |
| Netherlands | HD 620 S3 10-J | YMeKrvasdlwd 12/20 kV 3x95 Al rs +as35 (key read from a maker (Nedkab), the NEN text not seen) | Close | screen 25 → 35 mm² (HD 620 10-J Table A.3); Insulation screen (semicon) 0.6 → 0.8 mm; Sheath 3 → 3.2 mm; Overall diameter 59.53 → 62.51 mm; this cable as built misses 2 of its rules |
| India | IS 7098 (Part 2) | A2X2Y 3x95 12.7/22 kV (the code letters of IS 7098 (Part 2):2011 cl. 21.3) | Close | rated 12.7/22 kV (same Um 24 kV); Insulation 5.5 → 6 mm; Insulation screen (semicon) 0.6 → 0.8 mm; Wire screen material: not in the equivalent; this cable as built misses 2 of its rules |
No equivalent in: HD 620 S3 10-C (DIN VDE 0276-620) (no three-core cable at this voltage); BS 6622 (armoured cables only, asks a screen on each core); HD 620 S3 10-E1 (the size, cores or voltage would change); HD 620 S3 10-E2 (the size, cores or voltage would change); HD 620 S3 10-I1 (the size, cores or voltage would change); HD 620 S3 10-I2 (the size, cores or voltage would change); HD 620 S3 10-I3 (the size, cores or voltage would change); HD 620 S3 10-G (the size, cores or voltage would change); HD 620 S3 10-L (the size, cores or voltage would change); HD 620 S3 10-N (the size, cores or voltage would change); HD 620 S3 10-O (the size, cores or voltage would change); HD 620 S3 10-P (the size, cores or voltage would change).
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
AXCLJ-TT as the cable designer builds it, 3x95/25 12/20 kV
Overall diameter 59.5 mm, about 3,180 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Conductor screen (semicon) | Semiconducting | 0.60 | 12.7 |
| Insulation | XLPE | 5.1 | 22.9 |
| Insulation screen (semicon) | Semiconducting | 0.60 | 24.1 |
| Filler | Semiconducting | 51.9 | |
| Wire screen | Copper | 65 × 0.70 | 51.9 |
| Inner covering / bedding | Semiconducting | 0.60 | 53.1 |
| Laminate (radial water block) | Aluminium | 0.20 | 53.5 |
| Sheath | PE | 3.0 | 59.5 |
AXCLJ-TT on a drum
The smallest drum that passes every check, for 59.5 mm and about 3,180 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 63 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | KTG 28 (2800 mm flange), wood KTG drums (Europe), Bayka, KTG | 5 of 7 | 2,765–2,830 kg |
| 1,000 m | No single drum in KTG drums (Europe) takes it: the drum calculator splits it over several. | ||
Barrel at least 20 × OD = 1,191 mm for a cable of this kind (Medium voltage, multi-core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: AXCLJ-TT
AXCLJ-TT belongs to the family Medium voltage cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: Medium voltage cables
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Accessories for this cable
Terminations and joints for this cable, each with the range its typical kit sizes cover at this voltage. Such kits are tested to IEC 60502-4:2010 (Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV), Part 4: Test requirements on accessories for cables with rated voltages from 6 kV (Um = 7,2 kV) up to 30 kV (Um = 36 kV)).
- Heat shrink indoor terminations, Um 24 kV: conductor 25–630 mm²
- Heat shrink outdoor terminations, Um 24 kV: conductor 25–630 mm²
- Cold shrink indoor terminations, Um 24 kV: diameter over the insulation 14–50 mm
- Cold shrink outdoor terminations, Um 24 kV: diameter over the insulation 19–50 mm
- Slip-on outdoor terminations, Um 24 kV: conductor 25–1200 mm²
The kits are single core: on this three core cable one goes on each core.
Typical; no maker or kit is named, and your kit's own sheet decides.