Lead sheath (hydrocarbon and chemical barrier)

An extruded lead sheath keeps aromatic hydrocarbons and chemicals out of the insulation in contaminated ground.

Open in the designer with this requirement

Constructions that meet it

  • Lead sheath under the outer sheath: changes the cable's layers. Extruded lead (alloy) sheath over the inner covering, then bedding, armour and outer sheath (Pb). Drawbacks: Very heavy; lead is a restricted substance in some markets; fatigue under vibration; must be earthed.

Writing a tender? Pro writes this requirement into your specification, ready to copy. Open in the designer with this requirement · See Pro

Tests

No international test method: specifications state this in words. Tests that exist:

  • IEC 60502-1 / -2 (metallic sheath of lead): construction requirement (thickness by the standard); no hydrocarbon test. Pass: thickness

How specifications state it

Specified by construction ('lead sheathed', 'Pb'), not by a test.

Where it is asked for

  • refineries and petrochemical plants
  • tank farms
  • contaminated soil