FROR

FROR est une désignation de câble CEI-UNEL type names (Italy) : F = Conductor form: round flexible stranded, copper (no A before it) ('Conduttore a corda flessibile rotonda'); datasheet: class 5 flexible copper; R = 1st R, insulation: PVC compound, quality TI1/TI2, 70 C ('Mescola a base di PVC, qualità TI1 e TI2'); O = Cable form: cores laid up for a round cable ('Anime riunite per cavo rotondo'); R = 2nd R, sheath: PVC, quality TM1/TM2/RZ ('Guaina a base di PVC, qualità TM1, TM2, RZ'); datasheet TM2; FROR = FROR: flexible multicore control / power cable, class 5 copper, PVC insulation, cores laid up round, PVC sheath, 450/750 V. 450/750 V (Uo/U), 70 C max operating, 160 C short circuit, test voltage 2500 V (Redcavi). CEI 20-20/1 and IMQ CPT 007 (construction, Comcavi); EN 50525-1 (La Triveneta Flex-Oil O.R.); fire tests CEI 20-22 II, CEI EN 60332-1-2; designation per CEI-UNEL 35011.

1 système de codification reconnaît cette désignation

CEI-UNEL type names (Italy)

SymboleSignification
FConductor form: round flexible stranded, copper (no A before it) ('Conduttore a corda flessibile rotonda'); datasheet: class 5 flexible copper
R1st R, insulation: PVC compound, quality TI1/TI2, 70 C ('Mescola a base di PVC, qualità TI1 e TI2')
OCable form: cores laid up for a round cable ('Anime riunite per cavo rotondo')
R2nd R, sheath: PVC, quality TM1/TM2/RZ ('Guaina a base di PVC, qualità TM1, TM2, RZ'); datasheet TM2
FRORFROR: flexible multicore control / power cable, class 5 copper, PVC insulation, cores laid up round, PVC sheath, 450/750 V. 450/750 V (Uo/U), 70 C max operating, 160 C short circuit, test voltage 2500 V (Redcavi). CEI 20-20/1 and IMQ CPT 007 (construction, Comcavi); EN 50525-1 (La Triveneta Flex-Oil O.R.); fire tests CEI 20-22 II, CEI EN 60332-1-2; designation per CEI-UNEL 35011

Comportement au feu (RPC européen)

Une classe RPC est déclarée par le fabricant dans sa déclaration des performances et imprimée sur la gaine (EN 50575 art. 7). Ce décodeur n'en attribue aucune. Ce que signifient les classes RPC →

Sources : projet d'EN 13501-6 et projet final FprEN 50575:2014 (projets, et non les textes publiés) ; IEC 60332-3-24:2000+A1:2008 ; projet d'EN 13501-3 A2.