FROR

FROR ist ein Kabelkurzzeichen nach CEI-UNEL type names (Italy): F = Conductor form: round flexible stranded, copper (no A before it) ('Conduttore a corda flessibile rotonda'); datasheet: class 5 flexible copper; R = 1st R, insulation: PVC compound, quality TI1/TI2, 70 C ('Mescola a base di PVC, qualità TI1 e TI2'); O = Cable form: cores laid up for a round cable ('Anime riunite per cavo rotondo'); R = 2nd R, sheath: PVC, quality TM1/TM2/RZ ('Guaina a base di PVC, qualità TM1, TM2, RZ'); datasheet TM2; FROR = FROR: flexible multicore control / power cable, class 5 copper, PVC insulation, cores laid up round, PVC sheath, 450/750 V. 450/750 V (Uo/U), 70 C max operating, 160 C short circuit, test voltage 2500 V (Redcavi). CEI 20-20/1 and IMQ CPT 007 (construction, Comcavi); EN 50525-1 (La Triveneta Flex-Oil O.R.); fire tests CEI 20-22 II, CEI EN 60332-1-2; designation per CEI-UNEL 35011.

1 Kodiersystem erkennt dieses Kurzzeichen

CEI-UNEL type names (Italy)

SymbolBedeutung
FConductor form: round flexible stranded, copper (no A before it) ('Conduttore a corda flessibile rotonda'); datasheet: class 5 flexible copper
R1st R, insulation: PVC compound, quality TI1/TI2, 70 C ('Mescola a base di PVC, qualità TI1 e TI2')
OCable form: cores laid up for a round cable ('Anime riunite per cavo rotondo')
R2nd R, sheath: PVC, quality TM1/TM2/RZ ('Guaina a base di PVC, qualità TM1, TM2, RZ'); datasheet TM2
FRORFROR: flexible multicore control / power cable, class 5 copper, PVC insulation, cores laid up round, PVC sheath, 450/750 V. 450/750 V (Uo/U), 70 C max operating, 160 C short circuit, test voltage 2500 V (Redcavi). CEI 20-20/1 and IMQ CPT 007 (construction, Comcavi); EN 50525-1 (La Triveneta Flex-Oil O.R.); fire tests CEI 20-22 II, CEI EN 60332-1-2; designation per CEI-UNEL 35011

Brandverhalten (EU-Bauproduktenverordnung, CPR)

Eine CPR-Klasse erklärt der Hersteller in seiner Leistungserklärung und druckt sie auf den Mantel (EN 50575 Abschn. 7). Dieser Decoder weist keine Klasse zu. Was die CPR-Klassen bedeuten →

Quellen: Entwurf EN 13501-6 und Schlussentwurf FprEN 50575:2014 (Entwürfe, nicht die veröffentlichten Texte); IEC 60332-3-24:2000+A1:2008; Entwurf EN 13501-3 A2.