SER dimensions

Nominal calculation, not one manufacturer's datasheet. The conductors are compact aluminium as Southwire prints them; the XHHW-2 walls, the jacket and the ground are the values the makers print, because UL 854 was not read. Seven makers' cables of the same name differ by up to 20 % in diameter: check the datasheet before you specify or order.

Each row is one SER size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What SER means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 17 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
8-8-8-8600 V1.1414.7190
6-6-6600 V1.1414.9200
6-6-6-6600 V1.1416.8270
4-4-6600 V1.1417.1260
4-4-4-6600 V1.1419.2350
2-2-2-4600 V1.1422.4510
2-2-2-2-4600 V1.1425.1640
1-1-1-3600 V1.4025.5640
1/0-1/0-1/0-2600 V1.4027.6770
2/0-2/0-2/0-1600 V1.4029.9940
2/0-2/0-2/0-2/0-1600 V1.4033.51,190
3/0-3/0-3/0-1/0600 V1.4032.71,140
4/0-4/0-2/0600 V1.4031.41,020
4/0-4/0-4/0-2/0600 V1.4035.81,400
4/0-4/0-4/0-4/0-2/0600 V1.4040.11,770
250-250-250-3/0600 V1.6539.61,680
250-250-250-250-3/0600 V1.6544.42,130

Who makes or stocks this cable?