MC dimensions

Nominal calculation, not one manufacturer's datasheet. The conductors are NEC Chapter 9 Table 8; the THHN walls, the ground and the jacket are the values the makers print, and the armour band is derived from five makers' diameters, because UL 1569 was not read. Cables of the same name differ by up to 15 % over the armour: check the datasheet before you specify or order.

Each row is one MC size in copper at 600 V: the conductor from NEC Table 8, the walls as the makers catalogue them. Open a row for every layer and its source. What MC means, letter by letter.

North American building wire, 600 V (AWG / kcmil) · 23 sizes

SizeRatingInsulation mmOverall diameter mmWeight (approximate) kg/km
14/2600 V0.3811.4120
12/2600 V0.3812.3160
10/2600 V0.5114.0230
14/3600 V0.3812.0140
12/3600 V0.3813.1200
10/3600 V0.5115.0290
8/3600 V0.7618.2430
6/3600 V0.7620.7630
4/3600 V1.0224.3910
3/3600 V1.0226.11,140
2/3600 V1.0227.71,350
1/3600 V1.2730.91,670
3C 1/0 AWG600 V1.2731.81,980
3C 2/0 AWG600 V1.2734.22,400
3C 3/0 AWG600 V1.2737.03,000
3C 4/0 AWG600 V1.2740.03,660
3C 250 kcmil600 V1.5243.84,320
3C 300 kcmil600 V1.5246.75,120
3C 350 kcmil600 V1.5249.45,860
3C 400 kcmil600 V1.5251.96,620
3C 500 kcmil600 V1.5256.48,150
3C 600 kcmil600 V1.7861.89,740
3C 750 kcmil600 V1.7867.412,030