MC 10/3 600 V

Nominal calculation, not one manufacturer's datasheet. The conductors are NEC Chapter 9 Table 8; the THHN walls, the ground and the jacket are the values the makers print, and the armour band is derived from five makers' diameters, because UL 1569 was not read. Cables of the same name differ by up to 15 % over the armour: check the datasheet before you specify or order.

By NEC Table 8 and the catalogued walls, MC 10/3 600 V comes to an overall diameter of about 15.0 mm and a weight of about 290 kg/km.

Open this cable in the designer Change any layer, see it in 3D and to scale, and download it.

This size as a PDF datasheet under your brand, with Pro. See Pro

Request a quote for this cable Sent to makers of this cable family, free.

Main dimensions

ConductorCopper 10 AWG (5.3 mm²), Ø 2.6 mmNEC 2026 Chapter 9 Table 8: Class B concentric or solid diameter
InsulationPVC 0.51 mmMC conductor PVC insulation: the THHN / THWN-2 band of its size (Southwire SPEC 60103 / 60300 print it; UL 1569 not read)
Diameter over insulation3.6 mm
Core diameter3.8 mm
Overall diameter15.0 mm
Weight (approximate)290 kg/km

Layer by layer (inside out)

#LayerMaterialThickness mmØ over mmSourceHow firmly
1InsulationPVC0.513.6 (on each core)MC conductor PVC insulation: the THHN / THWN-2 band of its size (Southwire SPEC 60103 / 60300 print it; UL 1569 not read)maker catalogue value, standard text not read
2Nylon jacket (polyamide)Nylon (PA)0.103.8 (on each core)MC conductor nylon jacket: the THHN / THWN-2 band (UL 1569 not read)maker catalogue value, standard text not read
3Ground conductor: InsulationPVC0.513.6MC conductor PVC insulation: the THHN / THWN-2 band of its size (Southwire SPEC 60103 / 60300 print it; UL 1569 not read)maker catalogue value, standard text not read
4Ground conductor: Nylon jacket (polyamide)Nylon (PA)0.103.8MC conductor nylon jacket: the THHN / THWN-2 band (UL 1569 not read)maker catalogue value, standard text not read
5Separation tapePolyester0.109.4typical polyester tapetypical value, no rule
6Interlocked armourAluminium2.7915.0MC interlocked aluminium armour, radial band 0.110 in (2.79 mm): the median over 400 rows of five makers, the diameter under it computed; no maker prints the stripmaker catalogue value, standard text not read

Type MC is the UL 1569 metal-clad cable of NEC Article 330: THHN / THWN-2 conductors and a ground (green THHN to 1 AWG, bare copper from 1/0) cabled together under an assembly tape, in interlocked aluminium armour. Checked against Southwire, Atkore AFC, Encore, Cerrowire and Service Wire: research/designer-americas/mc-teck.md in the site repository.

Materials in this cable: Copper, Aluminium, PVC

Weight, by part

Conductors190 kg/km
Metal screens and armour60 kg/km
Insulation, semicon, tapes, fillers and sheaths40 kg/km
Total290 kg/km

Each layer's cross-section times its density; stranded conductors, laid-up cores and helical wires count 2 % longer than the cable. Densities: copper 8.89 and aluminium 2.703 g/cm³ (the values of IEC 60028 and IEC 60889); XLPE 0.92, PE 0.94, PVC 1.45, semicon 1.12, steel 7.85 g/cm³ (usual compound values).

Who makes or stocks this cable?

MC