YKYFOY
YKYFOY ist ein Kabelkurzzeichen nach PN (Poland): Y = PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names; K = kabel: power cable family (not a copper letter); Y = PVC insulation; Fo = Round steel wire armour; y = PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC); YKYFOY = YKYFoy: YKY with round steel wire armour and a PVC oversheath, 0,6/1 kV ((n): fire-retardant oversheath). 0,6/1 kV. PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue).
1 Kodiersystem erkennt dieses Kurzzeichen
PN (Poland)
| Symbol | Bedeutung |
|---|---|
Y | PVC sheath (the sheath under the armour or screen); the sheath letter comes first in Polish names |
K | kabel: power cable family (not a copper letter) |
Y | PVC insulation |
Fo | Round steel wire armour |
y | PVC protective oversheath extruded over the armour or screen (yn: fire-retardant PVC) |
YKYFOY | YKYFoy: YKY with round steel wire armour and a PVC oversheath, 0,6/1 kV ((n): fire-retardant oversheath). 0,6/1 kV. PN-93/E-90400; PN-93/E-90401; PN-HD 603 S1:2006/A3:2009 (as printed in the Elpar catalogue) |
Brandverhalten (EU-Bauproduktenverordnung, CPR)
Flammwidrig (y, YKYFOY). Die Einzelkabelprüfung hinter der Klasse Eca ist EN 60332-1-2 (die Flamme erlischt innerhalb von 425 mm). Gebündelte Kabel werden nach IEC 60332-3-24 Kategorie C geprüft (1,5 l/m, 20 min, Verkohlung höchstens 2,5 m); das ist keine Prüfung für eine CPR-Klasse, die CPR-Leiterprüfung für B1ca bis Dca ist EN 50399.
Eine CPR-Klasse erklärt der Hersteller in seiner Leistungserklärung und druckt sie auf den Mantel (EN 50575 Abschn. 7). Dieser Decoder weist keine Klasse zu. Was die CPR-Klassen bedeuten →
Quellen: Entwurf EN 13501-6 und Schlussentwurf FprEN 50575:2014 (Entwürfe, nicht die veröffentlichten Texte); IEC 60332-3-24:2000+A1:2008; Entwurf EN 13501-3 A2.