THHW
THHW is a NEC / UL (USA) cable designation: T = Thermoplastic (PVC) insulation; HH = High heat resistant, 90 C range (two H); W = Approved for wet locations; THHW = Thermoplastic high heat-resistant, moisture-resistant building wire. 600 V, 90 C dry, 75 C wet. UL 83; NEC Article 310.
3 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: UL 83 (edition 16): Thermoplastic-Insulated Wires and Cables. How the values are sourced
Worked reading of THHW 12 AWG, 600 V:
THHW: T = Thermoplastic (PVC) insulation; HH = High heat resistant, 90 C range (two H); W = Approved for wet locations; THHW = Thermoplastic high heat-resistant, moisture-resistant building wire. 600 V, 90 C dry, 75 C wet. UL 83; NEC Article 31012 AWG, 600 V: one core, copper 12 AWG (3.3 mm²); rated voltage 600 V
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
T | Thermoplastic (PVC) insulation |
HH | High heat resistant, 90 C range (two H) |
W | Approved for wet locations |
THHW | Thermoplastic high heat-resistant, moisture-resistant building wire. 600 V, 90 C dry, 75 C wet. UL 83; NEC Article 310 |
NEC Article 310 (US building wire, NFPA 70)
| Symbol | Meaning |
|---|---|
T | Thermoplastic Insulation |
HH | 90°C Insulation |
W | Moisture Resistant |
How to read a NEC Article 310 (US building wire, NFPA 70) cable code
NEC Article 400 (US flexible cords, NFPA 70 / UL 62)
| Symbol | Meaning |
|---|---|
T | Thermoplastic Insulation And Jacket |
H | Heater Cord |
H | Heater Cord |
W | Suitable For Use In Wet Locations And Sunlight Resistant |
How to read a NEC Article 400 (US flexible cords, NFPA 70 / UL 62) cable code
What is THHW cable?
THHW: Thermoplastic high heat-resistant, moisture-resistant building wire. Rating: 600 V, 90 C dry, 75 C wet. Standard: UL 83; NEC Article 310.
THHW is not described on the IAEI page; the letters follow its rules. The 90 C dry / 75 C wet split is NEC practice, UNVERIFIED in the research files.
Documents and pages the readings were taken from
THHW: equivalents in other countries
Shown for 1x3.31 600 V. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.
| Country | Standard | Name in that country | Verdict | Differences |
|---|---|---|---|---|
| International (IEC) | IEC 60502 | no letters for this build | Close | Insulation 0.76 → 1 mm; Overall diameter 3.79 → 4.27 mm |
Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.
THHW as the cable designer builds it, 12 AWG, 600 V
Overall diameter 3.8 mm, about 40 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.76 | 3.8 |
THHW on a drum
The smallest drum that passes every check, for 3.8 mm and about 40 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 14x10x5, wood NEMA reels (North America), Okonite | 15 of 18 | 22 kg |
| 1,000 m | NEMA 18x10x6, wood NEMA reels (North America), Okonite | 23 of 29 | 45 kg |
Barrel at least 20 × OD = 76 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: THHW
THHW belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²