TFXP-AL

TFXP-AL is a Norsk typebetegnelse (Norway) cable designation: T = 1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen - PEX'); F = 2nd letter: filler sheath or taping ('Fyllkappe/ båndering'); X = 3rd letter: no armour or screen ('Ingen armering e.l.'); P = 4th letter, outer sheath: PVC ('PVC'); the PE inner sheath is not in the code ('PE-kappen beskrives ikke i firebokstavkoden'); A = After the section (4G25A): aluminium conductor ('Flertrådet, glødet aluminiumsleder'; NEK: 'har aluminiumsledere'); AL = Written after the type name (TFXP AL): the same aluminium-conductor, green double-sheathed cable ('grønnpexen heter TFXP AL'); TFXP-AL = TFXP with aluminium conductor ('grønn-pex', Nexans TFXP 1 kV 4G25A): PEX core insulation, filler, inner PE sheath, green outer PVC sheath, 1 kV, for mains intake cable. 1 kV (Kabelboka heading 'TFXP 1kV'; Nexans web page read via search: 0,6/1 kV, 90 C). CENELEC HD 603-5M (Nexans Kabelboka p. 13); NEK Kabel names the type 'TFXP AL' (MR Flex sheet p. 19).

1 coding system recognises this code

Norsk typebetegnelse (Norway)

SymbolMeaning
T1st letter, insulation: cross-linked polyethylene, PEX ('Tverrbundet polyetylen - PEX')
F2nd letter: filler sheath or taping ('Fyllkappe/ båndering')
X3rd letter: no armour or screen ('Ingen armering e.l.')
P4th letter, outer sheath: PVC ('PVC'); the PE inner sheath is not in the code ('PE-kappen beskrives ikke i firebokstavkoden')
AAfter the section (4G25A): aluminium conductor ('Flertrådet, glødet aluminiumsleder'; NEK: 'har aluminiumsledere')
ALWritten after the type name (TFXP AL): the same aluminium-conductor, green double-sheathed cable ('grønnpexen heter TFXP AL')
TFXP-ALTFXP with aluminium conductor ('grønn-pex', Nexans TFXP 1 kV 4G25A): PEX core insulation, filler, inner PE sheath, green outer PVC sheath, 1 kV, for mains intake cable. 1 kV (Kabelboka heading 'TFXP 1kV'; Nexans web page read via search: 0,6/1 kV, 90 C). CENELEC HD 603-5M (Nexans Kabelboka p. 13); NEK Kabel names the type 'TFXP AL' (MR Flex sheet p. 19)

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

TFXP-AL: equivalents in other countries

Shown for 4x95 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)NA2XY 4x95 RM 0,6/1 kVEquivalentevery value the same

No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (not in its cable tables, armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.