TFXP

TFXP is a Norsk typebetegnelse (Norway) cable designation: T = 1st letter, insulation: cross-linked polyethylene, PEX ('T=Pexisolert'; Kabelboka: 'Tverrbundet polyetylen - PEX'); F = 2nd letter, bedding or filler sheath ('F=Fyllkappe'; Kabelboka: 'Fyllkappe/ båndering'); X = 3rd letter: no armour or screen ('X=Ingen armering/skjerm'; Kabelboka: 'Ingen armering e.l.'); P = 4th letter, outer sheath: PVC ('P=PVC-ytterkappe'); TFXP = TFXP: PEX-insulated, filler-sheathed, unarmoured, PVC-sheathed power and installation cable; the NEK Kabel MR Flex type has a flexible copper conductor, the A / AL type (separate entry) an aluminium one. 0,6/1 kV (NEK Kabel: 'Driftsspenning 0,6/1 [kV]', test 3,5 kV), 90 C conductor. HD 604-5D / HD 603-1 / IEC 60502-1 (NEK Kabel MR Flex sheet p. 5); HD 603-5M and NEK 536 (Nexans Kabelboka p. 13, 14).

2 coding systems recognise this code

Norsk typebetegnelse (Norway)

SymbolMeaning
T1st letter, insulation: cross-linked polyethylene, PEX ('T=Pexisolert'; Kabelboka: 'Tverrbundet polyetylen - PEX')
F2nd letter, bedding or filler sheath ('F=Fyllkappe'; Kabelboka: 'Fyllkappe/ båndering')
X3rd letter: no armour or screen ('X=Ingen armering/skjerm'; Kabelboka: 'Ingen armering e.l.')
P4th letter, outer sheath: PVC ('P=PVC-ytterkappe')
TFXPTFXP: PEX-insulated, filler-sheathed, unarmoured, PVC-sheathed power and installation cable; the NEK Kabel MR Flex type has a flexible copper conductor, the A / AL type (separate entry) an aluminium one. 0,6/1 kV (NEK Kabel: 'Driftsspenning 0,6/1 [kV]', test 3,5 kV), 90 C conductor. HD 604-5D / HD 603-1 / IEC 60502-1 (NEK Kabel MR Flex sheet p. 5); HD 603-5M and NEK 536 (Nexans Kabelboka p. 13, 14)

NEK 606

SymbolMeaning
TCross-Linked Polyethylene (XLPE)
FBedding Or Taping (Halogen-Free)
XNo Armour
PPolyvinylchloride - Pvc

How to read a NEK 606 cable code

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

TFXP: equivalents in other countries

Shown for 4x95 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)N2XY 4x95 RM 0,6/1 kVEquivalentevery value the same

No equivalent in: BS 5467 (armoured cables only); BS 6724 (armoured cables only, asks another sheath compound); BS 7846 (armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

Related cables