TFR-CV

TFR-CV is a KS / KEPCO type names (Korea) cable designation: TFR- = TFR-: tray flame retardant, a high flame-retardant PVC sheath for cable trays; C = C: cross-linked polyethylene (XLPE) insulation; V = V: PVC (vinyl) sheath; TFR-CV = TFR-CV: XLPE insulated tray cable with a flame-retardant PVC sheath, 0.6/1 kV (also 6/10 kV). 0.6/1 kV; 6/10 kV (Taihan p.16, p.21). KS C IEC 60502-1 (0.6/1 kV), KS C IEC 60502-2 (6/10 kV).

3 coding systems recognise this code

KS / KEPCO type names (Korea)

SymbolMeaning
TFR-TFR-: tray flame retardant, a high flame-retardant PVC sheath for cable trays
CC: cross-linked polyethylene (XLPE) insulation
VV: PVC (vinyl) sheath
TFR-CVTFR-CV: XLPE insulated tray cable with a flame-retardant PVC sheath, 0.6/1 kV (also 6/10 kV). 0.6/1 kV; 6/10 kV (Taihan p.16, p.21). KS C IEC 60502-1 (0.6/1 kV), KS C IEC 60502-2 (6/10 kV)

NBN (Belgian national cable names, ...B types)

SymbolMeaning
TTelephone Cable
FRFire Resistance Category
CConcentric Copper Conductor
VPolyvinyl Chloride (PVC)

How to read a NBN (Belgian national cable names, ...B types) cable code

Swiss cable codes (ASE/SEV wire codes and power cable codes)

SymbolMeaning
TThermoplastic Insulation And Jacket
FFlat Galvanized Steel Wire
RRound Steel Wire
CSteel Tape Armour
VReinforced (Electrically Or Mechanically)

How to read a Swiss cable codes (ASE/SEV wire codes and power cable codes) cable code

Fire behaviour (EU CPR)

  • Flame retardant (TFR-, TFR-CV). The single-cable test behind class Eca is EN 60332-1-2 (the flame stops within 425 mm). Bunched cables are tested by IEC 60332-3-24 category C (1.5 l/m, 20 min, char at most 2.5 m), which is not a CPR class test; the CPR ladder test for B1ca to Dca is EN 50399.

  • PVC sheath (TFR-, V, TFR-CV).

    Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):

    Listed as sources, alphabetically by maker. No maker pays to appear here.

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

TFR-CV: equivalents in other countries

Shown for 1x16 0.6/1 kV. Each country's rules are applied to this build, keeping the conductor, section, cores, voltage, screen, armour and sheath.

CountryStandardName in that countryVerdictDifferences
GermanyHD 603 5-G (DIN VDE 0276-603)N2XY 1x16 RM 0,6/1 kVCloseSheath 1.4 → 1.8 mm; Overall diameter 9.1 → 9.9 mm
IndiaIS 7098 (Part 1)2XY 1x16 1100 VCloserated 0.635/1.1 kV (same Um 1.2 kV); Sheath 1.4 → 1.8 mm; Overall diameter 9.1 → 9.9 mm; this cable as built misses 1 of its rules

No equivalent in: BS 5467 (not in its cable tables, armoured cables only); BS 6724 (not in its cable tables, armoured cables only, asks another sheath compound); BS 7846 (not in its cable tables, armoured cables only, asks another sheath compound).

Nominal values computed by each standard's rules, not manufacturer data. This is not a statement that two cables are interchangeable: the buyer's specification and the maker's type test decide.

TFR-CV as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.1 mm, about 210 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationXLPE0.706.3
SheathPVC1.49.1

TFR-CV on a drum

The smallest drum that passes every check, for 9.1 mm and about 210 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates within a few per cent of the cable makers' own tables: whole layers, wound diameter 1.05 × OD, 50 mm freeboard under the flange rim.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka11 of 13112 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG15 of 15241–245 kg

Barrel at least 20 × OD = 182 mm for a cable of this kind (Low voltage, single core): KTG table, the cable's datasheet wins. A load rating is the drum maker's own.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: TFR-CV

TFR-CV belongs to the family LV XLPE power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV XLPE power cables

Terms on this page: cable tray

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with TFR-CV

Related cables

More KS / KEPCO type names (Korea) designations