SJT
SJT is a NEC / UL (USA) cable designation: SJ = Junior service cord, 300 V, lighter duty; T = Thermoplastic (PVC) insulation and jacket; SJT = Junior thermoplastic flexible cord. 300 V, 60 to 105 C. UL 62; NEC Article 400, Table 400.4.
2 coding systems recognise this code
Standard, worked reading and related types
Standards behind these values: IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced
Worked reading of SJT 3/C 16 AWG, 300 V:
SJT: SJ = Junior service cord, 300 V, lighter duty; T = Thermoplastic (PVC) insulation and jacket; SJT = Junior thermoplastic flexible cord. 300 V, 60 to 105 C. UL 62; NEC Article 400, Table 400.43/C 16 AWG, 300 V: 3 cores, each copper 16 AWG (1.3 mm²); rated voltage 300 V
NEC / UL (USA)
| Symbol | Meaning |
|---|---|
SJ | Junior service cord, 300 V, lighter duty |
T | Thermoplastic (PVC) insulation and jacket |
SJT | Junior thermoplastic flexible cord. 300 V, 60 to 105 C. UL 62; NEC Article 400, Table 400.4 |
NEC Article 400 (US flexible cords, NFPA 70 / UL 62)
| Symbol | Meaning |
|---|---|
SJ | Junior Hard Service Cord (300 V, Hard Usage) |
T | Thermoplastic Insulation And Jacket |
How to read a NEC Article 400 (US flexible cords, NFPA 70 / UL 62) cable code
What is SJT cable?
SJT: Junior thermoplastic flexible cord. Rating: 300 V, 60 to 105 C. Standard: UL 62; NEC Article 400, Table 400.4.
Written "12/3": 12 AWG, 3 conductors counting the green ground.
Documents and pages the readings were taken from
Fire behaviour (EU CPR)
PVC sheath (T).
Typically targeted, as declared by makers for this kind of construction in the examples this site checked (not the class of this cable):
EcaN1XV-R, Ahlsell (seller)Cca-s3,d1,a3FG16OR16, Nexans (La Triveneta Cavi)EcaU1000 R2V, Nexans (La Triveneta Cavi)EcaN2XSY, Waskönig+Walter (10 kV datasheet)
Listed as sources, alphabetically by maker. No maker pays to appear here.
A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →
Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.
SJT as the cable designer builds it, 3/C 16 AWG, 300 V
Overall diameter 8.3 mm, about 90 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.
| Layer | Material | Thickness, mm | Over the layer, mm |
|---|---|---|---|
| Insulation | PVC | 0.76 | 3.0 |
| Filler | PP | 6.5 | |
| Separation tape | Paper | 0.10 | 6.7 |
| Sheath | PVC | 0.77 | 8.3 |
SJT on a drum
The smallest drum that passes every check, for 8.3 mm and about 90 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.
| Length | Drum size (its makers) | Layers | Gross weight |
|---|---|---|---|
| 500 m | NEMA 24x12x10, wood NEMA reels (North America), American Wire Group, Okonite | 14 of 16 | 55–58 kg |
| 1,000 m | NEMA 27x18x12, wood NEMA reels (North America), American Wire Group, Okonite | 15 of 18 | 105–107 kg |
Barrel at least 12 × OD = 99 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.
Other lengths, drums and weights: the cable drum calculator
Load it on a truck: 1000 m on its drum in the loading planner
Laying, sizes and datasheet: SJT
SJT belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables
Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²
Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro
Work with SJT
Who makes or stocks this cable?
Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.