SJT

SJT is a NEC / UL (USA) cable designation: SJ = Junior service cord, 300 V, lighter duty; T = Thermoplastic (PVC) insulation and jacket; SJT = Junior thermoplastic flexible cord. 300 V, 60 to 105 C. UL 62; NEC Article 400, Table 400.4.

2 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of SJT 3/C 16 AWG, 300 V:

  • SJT: SJ = Junior service cord, 300 V, lighter duty; T = Thermoplastic (PVC) insulation and jacket; SJT = Junior thermoplastic flexible cord. 300 V, 60 to 105 C. UL 62; NEC Article 400, Table 400.4
  • 3/C 16 AWG, 300 V: 3 cores, each copper 16 AWG (1.3 mm²); rated voltage 300 V

Related cable types: SJTO · SJTW · SJTOW · SJTOOW

NEC / UL (USA)

SymbolMeaning
SJJunior service cord, 300 V, lighter duty
TThermoplastic (PVC) insulation and jacket
SJTJunior thermoplastic flexible cord. 300 V, 60 to 105 C. UL 62; NEC Article 400, Table 400.4

NEC Article 400 (US flexible cords, NFPA 70 / UL 62)

SymbolMeaning
SJJunior Hard Service Cord (300 V, Hard Usage)
TThermoplastic Insulation And Jacket

How to read a NEC Article 400 (US flexible cords, NFPA 70 / UL 62) cable code

What is SJT cable?

SJT: Junior thermoplastic flexible cord. Rating: 300 V, 60 to 105 C. Standard: UL 62; NEC Article 400, Table 400.4.

Written "12/3": 12 AWG, 3 conductors counting the green ground.

Documents and pages the readings were taken from

NEC / UL (USA): how to read the cable type names

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

SJT as the cable designer builds it, 3/C 16 AWG, 300 V

Overall diameter 8.3 mm, about 90 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC0.763.0
FillerPP6.5
Separation tapePaper0.106.7
SheathPVC0.778.3

SJT on a drum

The smallest drum that passes every check, for 8.3 mm and about 90 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mNEMA 24x12x10, wood NEMA reels (North America), American Wire Group, Okonite14 of 1655–58 kg
1,000 mNEMA 27x18x12, wood NEMA reels (North America), American Wire Group, Okonite15 of 18105–107 kg

Barrel at least 12 × OD = 99 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: SJT

SJT belongs to the family North American cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: North American cables

Its sizes are in AWG and kcmil, which are not the same as the nearest mm²: compare them by area and by resistance. AWG to mm²

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with SJT

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More NEC / UL (USA) designations

SJT