RVV

RVV is a UTE (France, NF C 30-202 traditional system) cable designation: R = Cross-Linked Polyethylene (XLPE); V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC).

6 coding systems recognise this code

Standard, worked reading and related types

Standards behind these values: IEC 60502-1:2004 (edition 2.0): Power cables with extruded insulation and their accessories for rated voltages from 1 kV (Um = 1,2 kV) up to 30 kV (Um = 36 kV) - Part 1: Cables for rated voltages of 1 kV (Um = 1,2 kV) and 3 kV (Um = 3,6 kV); IEC 60228:2023 (edition 4.0): Conductors of insulated cables. How the values are sourced

Worked reading of RVV 1x16 0.6/1 kV:

  • RVV: R = Cross-Linked Polyethylene (XLPE); V = Polyvinyl Chloride (PVC); V = Polyvinyl Chloride (PVC)
  • 1x16 0.6/1 kV: one core, copper 16 mm²; rated voltage 0.6/1 kV

Related cable types: FR-VV · RVVP · RV-K · YVV · CVV · RHV

UTE (France, NF C 30-202 traditional system)

SymbolMeaning
RCross-Linked Polyethylene (XLPE)
VPolyvinyl Chloride (PVC)
VPolyvinyl Chloride (PVC)

How to read a UTE (France, NF C 30-202 traditional system) cable code

China (GB / JB/T / MT cable model codes)

SymbolMeaning
RFlexible Cable
VPolyvinyl Chloride (PVC)
VPolyvinyl Chloride (PVC)

How to read a China (GB / JB/T / MT cable model codes) cable code

CEI-UNEL 35011 (Italy)

SymbolMeaning
RMulti-Wire, Round-Section, Class 2
VImpregnated Glass Tape
VImpregnated Glass Tape

How to read a CEI-UNEL 35011 (Italy) cable code

UNE (Spain: UNE 21123 / UNE 20434)

SymbolMeaning
RCross-Linked Polyethylene (XLPE)
VPolyvinyl Chloride (PVC)
VPolyvinyl Chloride (PVC)

How to read a UNE (Spain: UNE 21123 / UNE 20434) cable code

NEN 3207 / KEMA (Netherlands)

SymbolMeaning
RVulcanised Rubber (Natural, SBR Or EPR, 60 °C)
VPolyvinyl Chloride (PVC)
VPolyvinyl Chloride (PVC)

How to read a NEN 3207 / KEMA (Netherlands) cable code

SS 424 17 01 (Sweden)

SymbolMeaning
RCopper Conductor, Many-Stranded, Flexible (Class 5)
VRubber Without Outer Sheath (Older Cables: Natural Rubber)
VEthylene-Propylene Rubber (EPR)

How to read a SS 424 17 01 (Sweden) cable code

How to read a UTE (France, NF C 30-202 traditional system) cable code

A UTE (France, NF C 30-202 traditional system) designation (France) is a row of letter groups, and each group stands for one part of the cable: conductor, insulation, screen, armour, sheath, or the standard it follows. The decoder knows 30 symbols for this system.

What does R mean in a UTE (France, NF C 30-202 traditional system) cable code? R means Cross-Linked Polyethylene (XLPE).

What does V mean in a UTE (France, NF C 30-202 traditional system) cable code? V means Polyvinyl Chloride (PVC).

Fire behaviour (EU CPR)

A CPR class is declared by the maker in its Declaration of Performance and printed on the sheath (EN 50575 cl 7). This decoder does not assign one. What the CPR classes mean →

Sources: EN 13501-6 draft and FprEN 50575:2014 final draft (drafts, not the published texts); IEC 60332-3-24:2000+A1:2008; EN 13501-3 draft A2.

RVV as the cable designer builds it, 1x16 0.6/1 kV

Overall diameter 9.9 mm, about 230 kg/km. Nominal values from the standard's tables for this size, computed, not a maker's data.

LayerMaterialThickness, mmOver the layer, mm
InsulationPVC1.07.1
SheathPVC1.49.9

RVV on a drum

The smallest drum that passes every check, for 9.9 mm and about 230 kg/km as the cable designer builds it. Drums as their makers print them; lengths are estimates: whole layers wound nested (each turn in the groove of the layer below), wound diameter 1.05 × OD, 50 mm freeboard under the flange rim. Cable makers' own tables print less, as they count aligned layers.

LengthDrum size (its makers)LayersGross weight
500 mKTG 6 (600 mm flange), plywood KTG drums (Europe), Bayka12 of 13122 kg
1,000 mKTG 8 (800 mm flange), wood KTG drums (Europe), Bayka, KTG16 of 16261–265 kg

Barrel at least 12 × OD = 119 mm for a cable of this kind (Flexible cable (class 5 or 6 conductor)): KTG table, the cable's datasheet wins. A load rating is the drum maker's own. A steel drum whose maker prints none is checked against the DIN 46391-4 guide load instead: 28 kN per m³ of gross winding volume.

Other lengths, drums and weights: the cable drum calculator

Load it on a truck: 1000 m on its drum in the loading planner

Laying, sizes and datasheet: RVV

Current rating and voltage drop: One circuit, C: cable on a wall, 30 °C air: about 76 A. At that current over 100 m, three-phase 400 V, cos φ 0.9: a voltage drop of about 4.4 %. Sources: IEC 60364-5-52:2009, Table B.52.4, p. 43; IEC 60228:2023 Table 5, p. 14; IEC 60228:2023 Annex B, p. 18; IEC 60364-5-52:2009 (ed. 3.0) Annex G (informative), pp. 74 to 75 (read in the standard text) Cable size calculator: smallest section for a load, every factor shown · Voltage drop calculator: IEC 60364-5-52 method and limits

RVV belongs to the family LV PVC power cables: the lowest laying temperature, bending radius, pulling, depth, drum handling and the test after laying, every rule with its sources. Laying and handling guide: LV PVC power cables

Selling this cable? Open it in the designer and get a datasheet with your logo (Pro). Open the cable designer · See Pro

Work with RVV

Who makes or stocks this cable?

Makers and stockists of this cable family appear here as sponsors for your region, each marked "Sponsored"; a listing never changes what this page says about the cable.

Related cables

More UTE (France, NF C 30-202 traditional system) designations

RVV